  Dimensions

Figure 1:

 Mount with the diaphragm in 

any vertical plane.

Figure 2: 

The sample line connections

 

for typical applications.

Figure 3:

 Before pressure is applied to 

the diaphragm, the switch contacts are in 

the normally closed (NC) position. 

Figure 4: 

Before pressure is applied to 

the diaphragm, the switch contacts are in 

the normally closed (NC) position. 

SPECIFICATIONS

MODEL  FS-751-112  

AIR  PRESSURE SENSING 

SWITCH 

WITH FIXED SET POINT

Mounting Position: 

Mount with the diaphragm in any vertical plane to 

obtain specified operating set point.

Set Point:

 

Fixed to operate on pressure rise at 

0.05±0.02"w.c.(1.27±0.508 mm) 

Switching Differential (Approximate):

 

0.02±0.01"w.c.

 

(0.508±0.254 mm w.c.)

Measured Media:

 

Air, or combustion byproducts that will not 

degrade silicone.

Maximum Pressure: 

½ psi (0.03 bar)

Operating Temperature Range:

   –40 ºFto 180 ºF
   (–40.0 ºC  to 82.2 ºC)

Life: 

100,000 cycles minimum at ½ psi maximum 

pressure each cycle and at maximum rated 

electrical load.

Electrical Rating: 

300 VA pilot duty at 115 to 277 VAC; 15 amp 

noninductive to 277 VAC, 60 Hz.

Contact Arrangement: 

SPDT

Electrical Connections: 

Screw-type terminals with cup washers.

Sample Line Connector: 

Two barbed ¼" connectors, suitable for slip-on 

flexible tubing.

Shipping Weight: 

1.2 lbs

Approvals: 

UL, CSA.