Bulletin LTFS751-112.02

Model 

FS-751-112

AIR PRESSURE SENSING SWITCH WITH FIXED SET POINT

APPLICATION

Model 

FS-751-112

 is an air flow proving 

switch designed for duct heater, oven, and 

other HVAC or Energy Management ap-

plications where an enclosure-protected, 

nonadjustable switch is required. 

FS-751-112

 

is  especially suitable for surface-mounting in 

areas where internal access is limited, and 

it is advisable to provide protection against 

accidental contact with the switch terminals. 

It can be used to sense positive, negative, or 

differential air pressure. The barbed sample 

line connections located on each side of the 

diaphragm accept flexible tubing.

GENERAL DESCRIPTION & 

OPERATION

The plated housing contains a diaphragm and 

a nonadustable snap-acting SPDT switch.

The SPDT snap action switch operates on 

pressure rise of 0.05"w.c., + 0.02" w.c.
 

MOUNTING (FIGURE 1)

Select a mounting location that is free from 

vibration. The 

FS-751-112

 must be mounted 

with the diaphragm in any vertical plane in 

order  to  maintain  the  specified  operating 

set point. Do not mount with the sample line 

connectors pointing upward. Surface mount 

via the two ⅛" diameter holes on the zinc-

plated strap bracket. The mounting holes 

are 3-

" apart.

AIR SAMPLING 

CONNECTION (FIGURE 2)

Model 

FS-751-112

 is designed to accept 

flexible tubing by means of barbed ¼" con

-

nectors. 
Locate the sampling probe a minimum of 

1.5 duct diameters downstream from the air 

source. Install the sampling probe as close 

to the center of the air- stream as possible.
Refer to 

Figure 2

 to identify the high pres-

sure inlet (

H

) and the low pressure inlet (

L

). 

Connect the sample lines as follows:

POSITIVE PRESSURE ONLY:  

Connect the 

sample line to inlet 

H

; inlet L re- mains open 

to the atmosphere.

NEGATIVE PRESSURE ONLY: 

Connect the 

sample line to inlet 

L

; inlet 

H

 re- mains open 

to the atmosphere.

TWO NEGATIVE SAMPLES:

 Connect the 

higher negative sample to inlet 

L

. Connect 

the lower negative sample to inlet 

H

.

TWO POSITIVE SAMPLES:

 Connect the 

higher positive sample to inlet 

H

. Connect 

the lower positive sample to inlet 

L

.

ONE POSITIVE & ONE NEGATIVE SAM-

PLE: 

Connect the positive sample to inlet 

H

. Connect the negative sample to inlet 

L

.

ELECTRICAL 

CONNECTIONS (FIGURES 2 

& 3)

Before pressure is applied to the diaphragm, 

the switch contacts will be in the normally 

closed (NC) position.  Wire control and alarm 

functions as shown in Figure 3. 