Cleveland Controls AFS–460 Скачать руководство пользователя страница 2

 (Figure  3)

ELECTRICAL CONNECTIONS 

(SEE FIGURE 3)

Before pressure is applied to the diaphragm, 

the switch contacts will be in the normally 

closed (NC) position as shown in 

Figure 3

.

The snap switch has screw top terminals 

with cup washers. Wire alarm or control ap-

plication as shown in 

Figure 4

.

 (Figure  4)

 (Figure  2)

SPECIFICATIONS 

MODEL AFS-460 AIR 

PRESSURE SENSING 

SWITCH WITH MANUAL 

RESET FEATURE

Mounting Position:

 

In order to meet lowest operating 

specifications, mount with the dia

-

phragm in any vertical plane.

Set Point Range:

 

0.40 ± 0.06"w.c. to 12.0"w.c.

Field Adjustable  

“Operate Range”:

 

0.46"w.c. to 12.0" w.c.

Measured Media: 

Air

Maximum Pressure:

 

½ psi (0.03 bar)

Life:

 

Exceeds UL-recognized mechanical 

endurance test of 6,000 cycles mini

-

mum at 0.5 psi maximum pressure 

each cycle and at maximum rated 

electrical load

Electrical Rating @ 60 Hz.:

 

15A @ 125, 250, or 277 VAC.

 

½ A @ 125 VDC, ¼ A @ 250 VDC.

 

¼ hp @ 125 VAC; ½ hp @ 250 VDC.

Contact Arrangement:

 

SPST–NC (manual reset)

Electrical Connections:

 

8-32 screw-top terminals with cup 

washers

Conduit Connection:

 

⅞" diameter opening accepts ½" 

conduit

Sample Line Connectors: 

Male, externally threaded 

7

16

" 24 UNS 

2A thread, complete with nut and self-

aligning ferrule

Sample Line Connections:

 

Connectors accept ¼" OD rigid or 

semi-rigid tubing

Approval and Recognition: 

UL, CSA, CE

Shipping Weight: 

1.2 lbs.

Accessories:

•  P/N 18311 Slip-on ¼" OD Tubing 

Adapter, suitable for slipping on flex

-

ible plastic tubing

•  Sample line probes
•  Orifice plugs (pulsation dampers)

FIELD ADJUSTMENT

The adjustment range of an

 AFS-460

 Air 

Switch  is 0.4" ± 0.06" w.c. to 12.0" w.c. To 

adjust the set point, turn the adjusting screw 

counterclockwise until motion has stopped. 

Next, turn the adjusting screw four complete 

turns in a clockwise direction to engage the 

spring. From this point, the next ten turns will 

be used for the actual calibration. 

Each full 

turn represents  approximately 1.16" w.c. 
Please note:  

To properly calibrate an  air 

switch, a digital manometer or other mea-

suring device should be used to confirm the 

actual set point.