CB780E/CB784E RELAY MODULES WITH VALVE PROVING
750-234
3
32-00150—03
a
The relay module must have a good earth ground providing a connection between the subbase and the control panel or
the equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in
event of an internal short circuit. The relay module requires a low impedance ground connection to the equipment
frame, which, in turn, requires a low impedance connection to earth ground.
b
2000 VA maximum connected load to relay module assembly.
c
Table 1. Terminal Ratings.
Terminal No.
Description
Ratings (120 Vac)
G
Flame Sensor Ground
a
—
Earth G
Earth Ground
—
L2(N)
Line Voltage Common
—
3
Alarm
1A pilot duty
120 Vac (+10%/-15%),
50 or 60 Hz (±10%).
4
Line Voltage Supply (L1)
b
5
Burner Motor
9.8AFL, 58.ALR (inrush)
6
Burner Controller and Limits Demand (Not Valve Proving)
1 mA.
7
Lockout/Running Interlock 8A run, 43A inrush
8A run, 43A inrush
8
Pilot Valve/Ignition
c
9
Main Fuel Valve
c
10
Ignition
c
F(11)
Flame Sensor
60 to 220 Vac, current limited
12
Firing Rate High Fire
75VA pilot duty
13
Firing Rate Common
75VA pilot duty
14
Firing Rate Low Fire
75VA pilot duty
15
Firing Rate Modulate
75VA pilot duty
16
Valve Proving Switch
1 mA
17
Demand—Valve Proving
1 mA
18
Low Fire Switch Input
1 mA
19
High Fire Switch Input (7800/40L only)
1 mA
20
Pre-Ignition Interlock Input
1 mA
21
Interrupted First Stage Oil Valve or MV2
c
22
Shutter
0.5A
Table 2. Combinations for Terminals 8, 9, 10, and 21.
Combination No.
Pilot Fuel #
Main 9
Ignition 10
Valve 21
1
C
F
No load
No load
2
B
F
No load
No load
3
No load
F
No load
B
4
F
F
A
No load
5
No load
F
A
F
6
D
F
A
No load
7
No load
D
A
D
8
D
D
A
No load
9
No load
D
A
D