PCS140e.1
24
750-329
APPENDIX C — Modbus Slave Addressing
Communications Parameters:
RS485, Half Duplex,9600/19.2k/38.4k Baud, No Parity, 8 Data Bits, 1 Stop Bit
Analog data is scaled 0-10,000. Apply the appropriate scaling factors to convert to site specific
engineering units.
PLC
Address
Description
Data Type
Modbus
Register
Units
Scaling
%AQ50
Header Pressure
Integer 16
40050
PSI
0-10000
%AQ51
Reserved
Integer 16
40051
%AQ52
Reserved
Integer 16
40052
%AQ53
Reserved
Integer 16
40053
%AQ54
Digital Input Word
Integer 16
40054
Bits
%AQ55
Digital Output Word
Integer 16
40055
Bits
%AQ56
Alarm Word
Integer 16
40056
Bits
%AQ57
Lead Pump
Integer 16
40057
Number
%AQ58
Lag 1 Pump
Integer 16
40058
Number
%AQ59
Lag 2 Pump
Integer 16
40059
Number
%AQ60
Lag 3 Pump
Integer 16
40060
Number
%AQ61
Pump 1 Hours (10,000s)
Integer 16
40061
Hours/10000
%AQ62
Pump 1 Hours (1s)
Integer 16
40062
Hours
%AQ63
Pump 2 Hours (10,000s)
Integer 16
40063
Hours/10000
%AQ64
Pump 2 Hours (1s)
Integer 16
40064
Hours
%AQ65
Pump 3 Hours (10,000s)
Integer 16
40065
Hours/10000
%AQ66
Pump 3 Hours (1s)
Integer 16
40066
Hours
%AQ67
Pump 4 Hours (10,000s)
Integer 16
40067
Hours/10000
%AQ68
Pump 4 Hours (1s)
Integer 16
40068
Hours
%AQ69
Integer 16
40069
%AQ70
Integer 16
40070
Alarm Word Bit Mapping (Register 40056)
Bit 0
Pump 1 Fault
Bit 1
Pump 2 Fault
Bit 2
Pump 3 Fault
Bit 3
Pump 4 Fault
Bit 4
Header Pressure LL
Bit 5
Header Pressure HH
Bit 6
Analog Signal Failure
Bit 7
Datalog SD Card Full
Bit 8
Pump 1 in Manual Mode
Bit 9
Pump 2 in Manual Mode
Bit 10
Pump 3 in Manual Mode
Bit 11
Pump 4 in Manual Mode
Bit 12
Source Tank LWCO
Bit 13
** Undefined Alarm14 **
Bit 14
** Undefined Alarm15 **
Bit 15
** Undefined Alarm16 **