FieldSmart FDP Indoor/Outdoor Wall Boxes
Installation Manual
_________________________________________________________
Manual 022793 REV A - March 2022
•
Use the hole on end of pad to
clean one alignment pin, then
press the end of the swab
into the other pin to clean.
•
Check your work with a fiber
scope. This can take several
attempts to get the endface
clean.
Female Connector (without pins)
•
Cleaned like a single fiber connector, using a cleaning platform. The
receptacles will be cleaned as long as you are using a combination clean
-
ing process as recommended.
•
Again, using a platen, moisten the platen with cleaning solvent on one
end to accommodate 3 swipes of the MPO female endface.
•
Holding the connector (If APC, slightly at an angle to accommodate for 8°
angle) swiping with medium pressure, from the wet area into the dry area
3 times, without wiping over previous area.
•
Inspect, and if clean, make the connection. If NOT, repeat above steps
until clean or if determined that the end face is damaged (based on stan
-
dards of 5 cleanings per connection), replace.