CLAUDGEN RCT250 / 500 MANUAL - (Radiant Ceiling Tile Heater)
The ceiling panels are manufactured from high quality, durable materials. To guarantee that your product functions optimally there are a few points of attention which
are described in the Installation Instructions. We can only offer you the full guarantee if this product is correctly installed in accordance with the Installation Instructions.
Carefully read the instructions prior to installation and ensure that you have the correct tools and materials. The electrical installation must be carried out by a qualified
electrician in accordance with IEE Regulations.
Technical information
Type
Output
Voltage
Amps
Max surface temp.
Measurements
Weight
RCT250
240W
230V
1.04
110
0
C
590 x 590mm
4,7 kg
RCT500
500W
230V
2.17
110
0
C
1190 x 590mm
8,5 kg
Class
: IPx4 Class 2
Colour
: White
Area of use
The ceiling heating panel is intended for the heating of rooms requiring free walls. The panel can be used for complete heating, or as an additional heater (e.g. over a reception
desk or other work place). There are two ratings: 240W and 500W. The heating panel provides mainly radiation heating. This implies that to obtain the same experienced
temperature it is possible to reduce the air temperature in the room, which saves energy. Because of the low surface temperature, max 110°C, the heating panel is suitable for
rooms with relatively low ceiling height. Thanks to the location, the panel is protected from any physical contact or damage. There is no risk of being burned.
Design
The ceiling heating panels are approved by KEMA for two applications:
- Ceiling mounting: Heating cassette is directly mounted to the ceiling using the included mounting brackets.
- Flush ceiling mounting: Heating cassette is intended as a lay-in panel for exposed grid.
Ceiling Heating Cassettes Installation Manual:
Installation
- The heater(s) should only be wired by a competent electrician, and in accordance with existing national regulations. The appliance should be preceded by an all pole
switch in accordance with existing regulations (not applicable to versions with a cord and plug).
-
Mounting height above floor shall be at least 1,8 m, l
ateral distance to wall shall be at least 50 mm. (See fig A)
- One or more units have to be connected to power line with a differential circuit breaker rated at 30 mA. The cable section has to be at least 1,5 mm2.
- Units with cable and plug can be interconnected using appropriate connection materials.
- The maximum power in interconnection is 2100W. If the units are to be extra insulated, then this insulation must not exceed a value of R=5 m2K/W.
- The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given
supervision or instruction
- Children being supervised not to play with the appliance.
- Allow disconnection of the appliance after installation, by accessible plug or a switch in the fixed wiring, unless a switch complying with a contact separation in all poles
of at least 3 mm.
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
2. Mounting
2.1 Integrated in ceiling, put in exposed grid (See fig A and B)
- Place the cassette in the required ceiling square. Minimum design height ”H” for dismounting, T-profile 32x15: 150 mm, T-profile 38x24: 200 mm. NOTE! Avoid fixing
vertical bars in the T-profile where a heating panel is to be installed. The panel fills out the whole square. It is recommended that the ceiling frame is adequately
supported.
- Connect the panel.
2.2 Bracket mounting (See fig A and C)
- When mounting in gypsum board, make sure that the panel frame is anchored in the beam behind. During long-term high temperatures the strength of the board is
reduced.
- Measure, drill and screw the panel frame to the ceiling.
- Hook the panel brackets to the panel frame on the ceiling
- Connect the panel.
Fig A
minimum distance
A: Ceiling 80mm
C: Obstacle 500mm
B: Wall
50mm
D: Floor 1800mm
Fig B
integrated in ceiling
Fig C
bracket mounting