Claudgen HE7230SL Скачать руководство пользователя страница 4

 

ENSURE THE AIR OUTLET OF HE7230SL/RX AND 

HE7245SL/RX IS NEAREST TO THE WALL OR      

CORNER.

 

3.1  Mounting 

 

The  Claudgen  recessed  ceiling  heaters  are  de-

signed to fit in place of a standard 600mm ceiling 

panel. 

 

IT IS ESSENTIAL THAT THE CEILING FRAME IS ADEQUATE 

TO  SUPPORT  THE  WEIGHT  OF  THE  HEATER,  OR  THAT 

THE  HEATER  IS  INDIVIDUALLY  SUPPORTED.    THERE  IS 

PROVISION  ON  THE  HEATER  FOR  CHAIN  OR  WIRE,  SUP-

PORT OR MOUNTING.

 

 

The  weight  of  the  HE7230SL/RX,  HE7245SL/RX  is 

7kg 

The weight of the HE7260SL/RX is 10kg 

 

It is the sole responsibility of the installer to ensure 

that  the  points  of  attachment  to  the  building  are 

sound. Care must be taken to allow complete free 

air  movement  into  the  inlet  grilles  of  the  unit  to 

ensure the  correct  working  operation of  the heat-

er. Carefully unpack the unit. The unit is supplied 

with a length of self-adhesive foam strip.  This can 

be cut into lengths and is to be laid on the 4 sides 

of the ceiling frame .  This will ensure that the unit 

assembly  is  free  from  vibration.    The  discharge 

grille and diffuser assembly can now be fitted into 

the ceiling frame. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.1  Electrical Connections.  

 

These  units  are  suitable  for  connection  to  a 

230/240 Volt 50 Hz single phase supply. 

 

The  appliance  shall  be  connected  to  the  supply 

via  an  appropriate  switched  fused  double  pole 

isolator  having  a  contact  separation  of  greater 

than 3mm. Test for correct operation and refit the 

cover. 

 

3. Installation Details. 

Fig.1 Air discharge of HE7230SL/RX and 

HE7245SL/RX 

 

Fig.2 Air discharge of HE7260SL/RX

 

TOP OR SIDE CABLE ENTRY 

 

TERMINAL COVER 

For  connection  to  the  mains  supply  it  will  be    

necessary to open  the terminal cover at the side/

back  of  the  unit  to  connect  the  supply  from  the 

controls prior to refitting the cover. Wire in accord-

ance to the wiring diagrams. 

 

For  safety  reasons,  a  sound  earth  connection 

must always be made to the unit before it is put to 

use. The unit should be wired in accordance with 

IEE  Regulations  for  the  Electrical  Equipment  of 

Buildings.

 

 

4. Electrical Connections. 

41001475 Iss 03 

Fig.3 Mounting supports

 

The wire or chain used to mount the heater can be 

attached  to  4  of  the  M6  studs  or  the  4  x  M6 

threaded inserts as shown in diagram.

 

Содержание HE7230SL

Страница 1: ...tails 3 Electrical Connections 4 Operation 5 Servicing Maintenance 6 41001475 Iss 03 Recessed Ceiling Heaters Catalogue Numbers HE7230SL HE7245SL HE7260SL HE7230RX HE7245RX HE7260RX Installation and O...

Страница 2: ...d that the electrical supply to the base unit in the heater is via an appropri ate switched isolator in accordance with the regulations in force in the country of use and must be via a fused isolator...

Страница 3: ...r ance allows for cable entry and prevents combustible surfaces overheating The minimum mounting height floor to grille is 2 2m for the HE7230SL RX 1 General Information HE7245SL RX and 2 5m for the H...

Страница 4: ...om vibration The discharge grille and diffuser assembly can now be fitted into the ceiling frame 4 1 Electrical Connections These units are suitable for connection to a 230 240 Volt 50 Hz single phase...

Страница 5: ...Fig 8 Heater with terminal cover open Fig 9 Terminal cover detail 41001475 Iss 03 5 2 RX Models The heaters HE7230RX HE7245RX and HE7260RX can be controlled by CONSORT wireless controller CRXSL The he...

Страница 6: ...uction of the free airflow by thermal cut outs If this happens the thermal cut outs switch off the appliance The ap pliance will not operate until the heater is discon nected from the mains supply and...

Страница 7: ...7...

Страница 8: ...contact our Helpline Consort Equipment Products Limited Thornton Industrial Estate Milford Haven Pembrokeshire SA73 2RT Tel 01646 692172 Fax 01646 695195 Email technical consortepl com Web www consort...

Отзывы: