background image

 

T H E   C O N T I N U O U S   P O W E R   C O M P A N Y

 

Page 11 

OPERATION 

nce the system has been properly installed, 
it is ready to operate.  The following 
procedures will explain how to start-up the 
system while plugged into rated electrical 

power and also how to start-up with no AC power 
available. 

Normal Operation on AC Start-Up: 

 

Verify that the unit is plugged into properly rated 
electrical power. 

 

Position the System Power Switch to the 

ON

 

position. 

The system will proceed through about a three 
second diagnostic where all the lights will sequence 

ON

 then 

OFF

.  The AC IN light will flash several times 

and the audible alarm will give a short burst.  The 
AC IN light will then stay 

ON

 and the battery level 

meter will light to at least an 80% level.  The 
INVERTER light will come 

ON

. and power will be 

available at all the output receptacles.  The LOAD I 
and LOAD II will come 

ON

Actual load may be connected at any time during 
this procedure, however power is only available 
when the light above either of the LOAD switches is 

ON

 continuously. 

Battery Operation after AC Start-Up: 

 

Unplug the unit from the standard wall outlet.

 

The AC ON light will flash at two to three second 
intervals.  Within 5 seconds, the audible alarm will 
sound at half-second intervals. 

 

Push and hold in the ALARM SILENT/TEST 
switch until the audible alarm is inhibited. 

If operation were to continue in this mode, the 
BATTERY LEVEL meter would start to turn 

OFF

, one 

light at a time starting from the top.  Once the last 
light is left and the preprogrammed battery 
availability time (usually about 2 minutes) is 
reached, the alarm will sound in a constant tone.  
Had the alarm been previously silenced, it would still 
re-enable to alert the user of limited operation.  This 
alarm can also be silenced as before.  If the unit is 
allowed to operate further, it will time out and shut 
off completely.  If power were to return, the unit will 
automatically restart and return to the condition it 
was in at the moment it went into 

Battery

 

Mode

DC Start Operation (Cold Start) 

If no utility power is available at the time backup 
power is required, the unit may be started to 
accomplish abbreviated tasks.  The limitations of the 
battery prevent extended operations at full load. 

 

Position the System Power Switch to the 

ON

 

position. 

 

Push and hold in the COLD START switch until 
the audible alarm beeps. 

The unit will start up similarly to normal AC start-up 
except the AC IN LED will continue to flash.  The 
LOAD outputs will come up in the 

OFF

 mode when 

using the COLD START feature. 

Loading the System 

The system can be loaded up to full rated load.  As 
load is applied, the LOAD METER will start to turn 

ON

.  Once full load is achieved, the full LOAD 

METER should be lit.  As additional load is applied, 
the top red OVERLOAD LED will come 

ON

.  If too 

much overload is applied, the audible alarm will 
sound.  If this increased load is not removed within 
five seconds, the unit will discontinue output 
operation and latch into an alarm condition.  The 
audible alarm will continue to sound and the ALARM 
LED will light.  Reducing the load and cycling the 
System Power Switch 

OFF

 then 

ON

 can reset the 

system. 

Programming the Outputs: 

The outputs on startup can be programmed 

ON

 or 

OFF

.  The default mode is programmed to turn both 

load circuits 

ON 

whenever you power up the UPS on 

AC startup.  They will stay energized until you turn 

OFF

 the UPS, the batteries run down during a power 

outage or if the appropriate load button is pressed. 
To program both loads to be 

OFF

 when the UPS is 

turned 

ON

 

Turn the UPS 

OFF.

 

 

Turn the UPS 

ON

 while pressing and holding the 

ALARM SILENT/TEST switch. 

 

The UPS will come 

ON

 with both loads 

OFF

 and 

will remember this setting each time the unit is 
turned 

ON

To program both loads to come 

ON

 

Turn the UPS 

OFF.

 

 

Turn the UPS 

ON

 while pressing and holding 

both LOAD I and LOAD II switches (this 
definitely requires both hands).  The UPS will 
remember this combination the next time it is 
powered 

ON

To program LOAD I or LOAD II to come 

ON

 

individually at startup: 

 

Turn the UPS 

OFF.

 

 

Turn the UPS 

ON

 while pressing and holding 

either LOAD I or LOAD II switches. 

The UPS will remember this combination the next 
time it is powered 

ON

.

  

Содержание DT1000R

Страница 1: ...s proprietary confidential and not to be disclosed disseminated or used except for the purpose provided by CLARY CORPORATION P N 510 12750 REV NR Date 2 2001 CLARY CORPORATION 1960 S Walker Avenue Mon...

Страница 2: ...BLE OF CONTENTS TITLE PAGE TABLE OF CONTENTS 2 INTRODUCTION 3 TECHNICAL DESCRIPTION 4 PACKAGING 6 PHYSICAL DESCRIPTION 7 INSTALLATION 10 OPERATION 11 SIGNALS AND INTERFACING 12 SPECIFICATIONS 13 CARE...

Страница 3: ...nce of the UPS and batteries Be aware of the following symbols and their meaning as they appear throughout the manual This equipment generates and uses radio frequency energy and if not installed and...

Страница 4: ...the supply components that keep the entire system operational Production downtime can now be virtually eliminated by knowing exactly what patterns the supply utility power maintains and by knowing ex...

Страница 5: ...T H E C O N T I N U O U S P O W E R C O M P A N Y DT1000R ET UPS BATTERY BANK SIMPLIFIED SYSTEM INTERCONNECT DC IN AC IN...

Страница 6: ...there is significant damage to the carton or if there is any physical damage to this unit report this to your carrier These units are encapsulated in a protective wrap that comes apart once the produc...

Страница 7: ...witches always hold the switch in for at least two seconds to insure function confirmation This feature has been implemented into the system design to avoid inadvertent operation of any of the user av...

Страница 8: ...communications signals 19 Signal Open collector signal contacts 20 AC In Input receptacle for all AC power 21 DC In Input receptacle for all DC power 23 SYSTEM GROUNDING STUD 24 SNMP Option Slot for s...

Страница 9: ...cessful transition Load II A momentary push button switch that works identical to LOAD I except it corresponds to the LOAD II AC output receptacles at the panel Alarm Silent Test A momentary push butt...

Страница 10: ...The air inlets vents and fan should not be obstructed or blocked in any way The more breathing space the system has the cooler it operates The air should remain free from excessive dust and chemical...

Страница 11: ...Mode DC Start Operation Cold Start If no utility power is available at the time backup power is required the unit may be started to accomplish abbreviated tasks The limitations of the battery prevent...

Страница 12: ...tdown has been accomplished The system may be configured to shutdown by applying a 5 to 12V signal across the appropriate pins Contact the factory for configuration details RS232 is a true communicati...

Страница 13: ...8 0 457 Weight Lbs Kg HxWxD 30 13 5 DESIGN Standard Features Power Factor Corrected Digital Regenerative On Line Sinewave Inverter Powers Load Continuously Extended Brownout Protection Designed for No...

Страница 14: ...en or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The...

Страница 15: ...actory In consulting the factory always have the unit model number and serial number at hand This information is located on the identification label and is essential in retrieving your unit s performa...

Страница 16: ...Page 16...

Отзывы: