Measure Limiting Voltage (8/20 µs @ 3 kA) - MLV

CARACTERÍSTICAS TÉCNICAS

TECHNICAL CHARACTERISTICS

CLAMPER Light MOV 12P

CLAMPER Light MOV 22P

Modelos | Models

Maximum discharge current @ 8/20 µs - I

máx.

Protection modes

Typical response time

Number of protected conductors

Operating frequency

Nominal operating voltage - U

0

W (2 ms)

máx. 

Nominal discharge current @ 8/20 µs - I

n

Installation scheme

Measure Limiting Voltage (8/20 µs @ I ) - MLV

N

Maximum continuous operating voltage - U

c

Reference voltage @ 1 mA

22 kA

10 kA

L/N: 1500 V | L/G: 1750 V | N/G: 1750 V

L/N: 1100 V | L/G: 1200 V | N/G: 1200 V

  L/N (differential mode); L/G - N/G (common mode)

< 25 ns

2

50 - 60 Hz

12 kA

5 kA 

320 V

120 / 277 V

L/N: 1120 V | L/G: 1250 V | N/G: 1250 V

510 V

L/N: 1070 V | L/G: 1200 V | N/G: 1200 V

In parallel with load

330 J

Protection technology

Metal Oxide Varistor (MOV)

Tecnología de protección

Varistor de Óxido Metálico (MOV)

Modos de protección

Nota:
El varistor de óxido metálico (MOV) puede fallar en el modo de cortocircuito si se trabaja en condiciones superiores 
al parámetro máximo o al final de su vida útil. Se debe instalar cierta protección de respaldo.

Note: 
Metal Oxide Varistor (MOV) may fail in short circuit mode if work under condition greater than maximum parameter 
or end of life. It must be installed certain backup protection.

Tiempo de respuesta típico

L / N (modo diferencial); L / G - N / G (modo común)

Número de conductores protegidos

Tensión nominal de funcionamiento - U

0

Frecuencia de operación

Tensión máxima de funcionamiento continuo - U

c

Tensión de referencia @ 1 mA

Corriente nominal de descarga @ 8/20 µs - I

n

Corriente de descarga maxima @ 8/20 µs - I

máx.

Modo de instalación

En paralelo con la carga

4

Tensión residual (8/20 µs @ 3 kA)

Tensión residual (8/20 µs @ I )

N