DEX ELECTRONIC MPS®
24
EN
Structural prerequisites
• The appliance must be installed via a permanent connection. Heater must be
earthed! A cable size of 10 mm
2
must be observed.
• The electric wiring should not be injured. After mounting, the wiring must not be
direct accessible.
• An all-pole disconnecting device (e.g. via fuses) with a contact opening width of at
least 3 mm per pole should be provided at the installation end.
• To protect the appliance, a fuse element must be fitted with a tripping current com-
mensurate with the nominal current of the appliance.
2
1
4
5
3
7. Electrical connection
Wiring diagram
Only by a specialist!
Please observe:
• VDE 0100
• The installation must comply with current IEC and national local regulations or
any particular regulations, specified by the local electricity supply company
• The rating plate and technical specifications
• The unit must be earthed!
1. Electronic circuitry
2. Heating element
3. Safety pressure cut-out
4. Terminal strip
5. Safety thermal cut-out