background image

Page 18

 

   EI 

Man 

u al

Diagnostics

Step 1D -

  Press 

 

and 

 simultaneously for 5 seconds and release. If screen in Step 2D does not appear 

the lock on the valve is activated. To unlock press 

, NEXT, 

,

 

REGEN in sequence, then press 

 

and 

 

simultaneously for 5 seconds and release.

Step 1D

Step 2D –

 Software Version. Press NEXT to go to Step 3D. Press REGEN to exit Diagnostics.

Step 2D

Step 3D –

 Volume, total used since start-up: This display shows the total cubic meters treated since startup. 

0 M

3

 will be shown when a water meter is not installed. Press the NEXT button to go to Step 4D. Press 

REGEN to return to previous step.

Step 3D

Step 4D –

 Days, total since start-up: This display shows the total days since startup. Press the NEXT button 

to go to Step 5D. Press REGEN to return to previous step.

Step 4D

Step 5D –

 Regenerations, total number since start-up: This display shows the total number of  regenerations 

that have occurred since startup. Press the NEXT button to go to Step 6D. Press REGEN to return to 
previous step.

Step 5D

Step 6D –

 Error Log: This display shows a history of the last 10 errors generated by the control

during operation. Press 

 

or 

 to view each recorded error. 

Press NEXT to go to Step 7D. Press REGEN to return to previous step.

Step 6D

Step 6D –

 Error Log: This display shows a history of the last 10 errors generated by the control

during operation. Press 

 

or 

 to view each recorded error. 

Press NEXT to go to Step 7D. Press REGEN to return to previous step.

Step 7D –

 Days, since last regeneration: This display shows the days since the last regeneration occurred. 

Press NEXT to go to Step 8D. Press REGEN to return to previous step.

Step 7D

Step 8D –

 Volume, since last regeneration: This display shows the volume of water that has been treated 

since the last regeneration. 0.00 M

3

 will be shown when a water meter is not installed. Press NEXT to go to 

Step 9D. Press REGEN to return to previous step.

Step 8D

Содержание Water Specialist EI

Страница 1: ...Water Specialist EI Control Valve Programming and Cover Drawing Manual...

Страница 2: ...Page 2 EI Manual...

Страница 3: ...EI Front Cover and Drive Assembly 4 Regeneration and Error Screens 5 User Displays 6 Configuration Settings 7 OEM Softener System Setup 11 Setting Options Table 14 OEM Filter System Setup 15 Installer...

Страница 4: ...ront Cover and Drive Assembly AC Adapter U S International Supply Voltage 120V AC 230V AC Supply Frequency 60 Hz 50 Hz Output Voltage 15VDC 15VDC Output Current 500 mA 500 mA 1 Battery replacement is...

Страница 5: ...user cannot cancel this request except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds Regeneration Cycles and Times Button Operation and Function Changes variable bei...

Страница 6: ...turn to the User Displays Time of day should only need to be set after power outages lasting more than 8 hours if the battery has been depleted and a power outage occurs or when daylight saving time b...

Страница 7: ...ignal or one dP switch cannot be used for both controls on0 If the dP switch is closed for an accumulative time of 2 minutes a regeneration will be signaled to the unit In a twin alternating system th...

Страница 8: ...peration For separate source operation the three wire communication cable is not used Selection requires that a connection to a Clack Motorized Alternator Valve MAV is made to the two pin connector la...

Страница 9: ...rvice Position MAV piston rod Extended WS1 WS1 25 and WS1 5 Valves For Clack Corporation alternator systems using WS1 WS1 25 and WS1 5 valves there will be an option to delay the last two cycles of re...

Страница 10: ...o Hard Water Bypass V3097 BSPT or V3098 BSPT to the two pin connector labeled MAV located on the printed circuit board is required Press NEXT to go to Step 6CS Press REGEN to return to previous step S...

Страница 11: ...he brine tank after the final rinse or PrE to refill the brine tank four hours before the regeneration time set This screen is not viewed when Step 2S is set to Filtering Press NEXT to go to Step 5S P...

Страница 12: ...matically calculated and reserve capacity will be automatically estimated oFF regeneration will be triggered solely by the day override setting see Installer Display Settings Step 4I a volume regenera...

Страница 13: ...e meter Ranges from 1 to 200 liters Press NEXT to go to Step 15S Press REGEN to return to previous step Step 15S Set Relay Deactivate Time using or If Set Time on is selected in Step 13S the relay wil...

Страница 14: ...be allowed to be set because regeneration will always occur when volume capacity reaches 0 Any number on 0 oFF Reserve capacity NOT automatically estimated Regeneration occurs immediately when volume...

Страница 15: ...M3 See Setting Options Table for more detail Press NEXT to go to Step 6F Press REGEN to return to previous step Step 5F Step 6F Set Regeneration Time Options using or If value is set to NORMAL means r...

Страница 16: ...from 1 second to 20 minutes Press NEXT to exit OEM Filter System Setup Press REGEN to return to previous step Step 9F EXIT OEM FILTER SYSTEM SETUP Step 7F Set Relay Operation using or The choices are...

Страница 17: ...ximum number of days between regenerations If value set to oFF regeneration initiation is triggered solely by volume used If value is set in days allowable range from 1 to 28 regeneration initiation w...

Страница 18: ...shows the total number of regenerations that have occurred since startup Press the NEXT button to go to Step 6D Press REGEN to return to previous step Step 5D Step 6D Error Log This display shows a hi...

Страница 19: ...f A then the tank with the valve on it was in service if b the tank with the in out head on it was in service The next three digits represent the number of hours ago that the transfer occurred The dis...

Страница 20: ...Page 20 EI Manual...

Страница 21: ...EI Manual Page 21...

Страница 22: ...Page 22 EI Manual...

Страница 23: ...History 3 12 2015 PAGE 12 Step 13S Clarified relay operation PAGE 16 Step 7F Clarified relay operation 11 16 2016 PAGE 17 Step 3I updated text PAGE 4 Updates to table and drawing Bracket and Spring C...

Страница 24: ...Page 24 EI Manual Form No V3435EI 8 24 2017 U S Patents 6 402 944 6 444 127 6 776 901...

Отзывы: