WS2H Control Valve Manual
Page 17
Timer Screens (continued)
TIMER 2
Set output 1.
These settings will only be allowed with the system board installed.
Time: Relay is turned on after specifi ed time from the start of regen and is left on for a specifi ed time.
Cycle: Relay is turned on after the start of a specifi ed cycle and is left on for a specifi ed time.
Volume: Relay is turned on, during service fl ow only, every specifi ed number of volume units and is left on for a specifi ed time.
Volume & Regen: Relay is turned on every specifi ed number of volume units, and is left on for a specifi ed time.
STbY: Relay would be used to control external valving, closing for unit regeneration, or when it would be offl ine in system operation.
REGEN: Relay closes when the unit is in regen.
Err: Relay closes when the unit is in any error mode.
TIMER 3
Set output 2.
These settings will only be allowed with the system board installed.
Time: Relay is turned on after specifi ed time from the start of regen and is left on for a specifi ed time.
Cycle: Relay is turned on after the start of a specifi ed cycle and is left on for a specifi ed time.
Volume: Relay is turned on, during service fl ow only, every specifi ed number of volume units and is left on for a specifi ed time.
Volume & Regen: Relay is turned on every specifi ed number of volume units and is left on for a specifi ed time.
STbY: Relay would be used to control external valving, closing for unit regeneration, or when it would be offl ine in system operation.
REGEN: Relay closes when the unit is in regen.
Err: Relay closes when the unit is in any error mode.
TIMER 4
Select output 1, On trigger set point, per units previously selected.
This screen will not display if the unit does not have a system board, or if STbY was selected as the trigger.
Time: Time after the start of a regen before switch is closed.
Cycle: Select a cycle which will close output 1.
Volume: Volume of water interval during service between switch closures.
Timer 4 and 6 screens will not display if display if STbY, REGEN or Err are selected in TIMER 2 and TIMER 3.
TIMER 5
Select output 1 On duration before turning OFF. This screen will
not display if the unit does not have a system board.
TIMER 6
Select output 2, On trigger set point, per units previously selected.
This screen will not display if the unit does not have a system board, or if
STby was selected as the trigger
Time: Time after the start of a regen before switch is closed.
Cycle: Select a cycle which will close output 2.
Volume: Volume of water interval during service between switch closures.
TIMER 7
Select output 2 On duration before turning OFF.
This screen will not display if the unit does not have a
system board.
Relay Trigger Settings
Trigger
Units
Range
Increments
Time
Minutes
:01-20:00
:01
Cycle
Slow Rinse
Volume
Gallons
1-200
200-1000
100-10000
1
5
10
Volume
Liters
1-760
760-13800
13800-38000
4
19
38
Relay Duration Settings
Trigger
Units
Range
Increments
Time
Minutes
:01-20:00
:01
Return To
Normal Operation.
TIMER 2
TIMER 2
TIMER 3
TIMER 4
TIMER 5
TIMER 6
TIMER 7