for remote signal alarm of Failure To Develop Pressure.  

K.) Terminals 18 and 19 are dry-contact type (N.O. rated: 1 

Amp, 120 VAC) for connection to customer supplied circuit 
for remote signal alarm of Loss Of Pressure.  

L.) Terminals 20 and 21 are dry-contact type (N.O. rated: 1 

Amp, 120 VAC) for connection to customer supplied circuit 
for remote signal alarm of Valve Fail To Open.

M.)Terminals 22 and 23 are dry-contact type (N.O. rated: 1 

Amp, 120 VAC) for connection to customer supplied circuit 
for remote signal alarm of Valve Re-Closed during start 
sequence.  

N.) Terminals 24 and 25 have 120/60 AC power (N.O. up to 1 

Amp - fused at F4) present when an alarm condition exists 
and are for connection to customer supplied circuit for 
remote signal alarm of Loss Of Power Restart Delay.  
Typically, this would activate a relay for the alarm signal.

O.)Terminals 26 and 27 are dry-contact type (N.O. rated: 1 

Amp, 120 VAC) for connection to customer supplied circuit 
for remote signaling of the H-O-A switch being in the "Auto"
position.  When the H-O-A switch is in the "Auto" position, 

no power contact is "made" at these terminals.  

P.) Terminals 28 and 29 are dry-contact type (24 volt DC, 10 

Milliamp) for connection to customer supplied no-voltage 
circuit to provide an "Anti-Plugging" input signal from the 
pump (if so equipped) when the pump is coasting or spinning
in reverse.  When these contacts are "made" from the pump,
a start sequence will not be allowed.

OPERATION CHECK OUT AND BENCH TEST

The following steps are for a PC-1 operation check out and bench
test.  This test is for newer PC-1 panels built since January 1998
and that have on the lid face the following: a) Lamp-test/Reset
switch, b) H-O-A switch mounted to the left-of-center, c) lid has red
and blue color markings on white background, and d) inside the
PC-1 is an Automation-Direct brand modular-style PLC.  PC-1’s
built before September 1996 used an Omron brand dedicated PLC
for internal control sequencing and does not follow this sequence
exactly.

Preparation:

A.) PC-1 hooked up to 120/60 VAC at terminals 1, 2, and Ground.
B.) No other inputs or outputs hooked up to the PC-1.
C.) Set Time Delay Relays TR1, TR2, and TR3 to zero time.
D.) H-O-A switch is in OFF position.

The following steps occur when power is applied:

1. On the lid, the white panel light (Power) goes on.
2. On the inside, the CPU module PWR and RUN green 

indicators go on.

3.  On the inside, the Input module red indicators A0, A7, and 

B0 go on (use A/B selector switch to switch between A and 
B series).

4.  On the inside, the TR1 relay ON and OUT lights are on.

NOTE:

If the white panel light does not go on, then the E-STOP

switch is depressed.  Lifting the E-STOP switch will turn on white
panel light.  The switch must "click" into place.

NEXT, turn the H-O-A switch from OFF to HAND, then push green
(Start) button.  Watch for:

1. On the lid, the blue panel light (Pressure) goes on and about 

three seconds later the green panel light (Valve Open) goes on.

2. On the inside, the Input module red indicator lights A3, A5, 

A6, A7, B0, and B4 go on.

3. On the inside, the TR1, TR2, and TR3 relay ON and OUT

lights go on.

4. On the inside, the CR1 relay red indicator light goes on.

NOTE:

a) To verify that panel lamps are functionary properly, depress

and hold Lamp Test/RESET button.  All five panel lights  g o
on for about three to five seconds and then go off.  

b) If the amber panel light (Restart/Delay) flashes, then 

depress the Lamp Test/RESET button for at least 30 
seconds to reset the PC-1.  You may hear some relay 
clicking from inside the PC-1, this is normal.  If AC power 
to terminals 1, 2, and ground are removed for 30 seconds, 
the PC-1 will also reset.

c) If the Lamp Test/RESET button is released before complete

reset, then when the HOA switch is turned from OFF to 
HAND (or if it was already in HAND), AND then Start button
is pushed, the amber panel light will flash.  A complete 30 
second reset will turn off flashing amber panel light. 

d) If the Lamp Test/RESET button is released before complete

reset and the amber panel is flashing, THEN when the E-
STOP switch is depressed and then lifted, the red panel 
light goes on and the amber panel light will continue to flash.
A complete 30 second reset will turn off red panel light and 
flashing amber panel light.

CLA

-

VAL 

        

Copyright Cla-Val 2006   Printed in USA   Specifications subject to change without notice.

   P.O. Box 1325 

 Newport Beach, CA 92659-0325 

 Phone: 949-722-4800 

 Fax: 949-548-5441 

 E-mail: [email protected] 

 Website cla-val.com 

©

N-PC-1  (R-8-06)

Содержание PC-1

Страница 1: ...le length Avoid running wires near high energy wiring Avoid running input wiring in close proximity to output wiring where possible Avoid creating sharp bends in the wires Input Power Provide 5 amp fu...

Страница 2: ...powered 7 Valve Reclosed Remote Alarm Output Circuit non powered 8 Loss of Power Restart Delay Alarm Output Circuit 120 60 VAC powered 9 H O A Switch in Auto Position Remote Contacts Output Circuit n...

Страница 3: ...panels built since January 1996 Refer to Field Wiring Hookup dia gram Cla Val drawing 204377 included with this manual A Terminals 1 2 and Ground are for connecting 120 Volt 60Hz AC 5 Amp fused power...

Страница 4: ...y Relays TR1 TR2 and TR3 to zero time D H O A switch is in OFF position The following steps occur when power is applied 1 On the lid the white panel light Power goes on 2 On the inside the CPU module...

Страница 5: ...Energized Closed Stopping Loss of Pump Discharge Pressure During Operation REQUIRES Manual RESET for Restart Pressure Switch ON ON OFF OFF Flashing 1 Amp DRY Contacts 18 19 De Energized De Energized C...

Страница 6: ...to System Booster PUMP 60 Series Control Valve Pump MOTOR STARTER H O A Radio I O RTU H O A Relay Radio 2 S2 COM 1 1 S1 N O V2 V1 2 4 5 7 8 10 11 13 12 G Cla Val PC 1 120 VAC 1R L H N 1 2 Pump Panel 1...

Страница 7: ...m Well PUMP Check Valve 61 Series Control Valve Pump MOTOR STARTER H O A Radio I O RTU H O A Relay Radio 2 S1 N O 1 1 S2 COM V1 V2 2 4 5 7 8 10 11 13 12 G Cla Val PC 1 120 VAC SCADA Center 1R To Waste...

Отзывы: