Installation Data

For Controlling Hytrol Valve

The float control is mounted above the high

water level in the tank. The valve is installed

in  the  line  leading  to  the  tank  and  is

connected to the float control pilot by tubing.

(Min. 

3

8

" tubing)

When line pressure is used to operate the

valve, tubing connections are made from the

float control pilot to the valve cover, and also

to the inlet side of the valve. An X46 Flow

Clean Strainer must be installed in the inlet

side  of  the  valve.  The  control  may  be

installed at any elevation above the valve,

providing that the flowing line pressure in psi

is equal to, or greater than, the vertical

distance in feet between the valve and the

float control.
A clean independent source of air or water

may be used to operate the valve. The

pressure from this independent source must

constantly  be  equal  to  or  greater  than

pressure at the valve inlet. The independent

source is connected to the float control pilot

in place of the supply line connected to the

inlet side of the valve. If the Model 100-01

under the control of the CF1-C1 is 8" or

larger,  auxiliary  Hytrol  valves  may  be

required. Consult factory for details.

For Controlling

Powertrol Valves

          Float Up                 Float Up

   Closes Valve                 Opens Valve

When Ordering, Please Specify

1.    Catalog No. CF1-C1
2.    Size and type of Valve to be 

       controlled.

3.    Material if different from standard
4.    Float rod length if longer than 2 ft.

NOTE:

1) A stilling well (Min. 8" I.D.) must be

provided around the float.
2) Must be inspected periodically.

Float Up Closes Valve

Float Down Closes Valve

Float Position     Valve 1       Valve 2

         

UP               CLOSED         OPEN

       DOWN              OPEN         CLOSED

Operation

Stilling

Well

Flow

CF1-C1

X43 or 

X46

Strainer

Supply

(Operating Pressure)

Port 2

Port 1

(Plugged)

Drain

Supply

(Operating Pressure)

Port 2

Port 1

Drain

Supply

(Operating Pressure)

Port 2

Port 1

Drain

Supply

(Operating Pressure)

Port 2

Port 1

Drain

Valve 1

Valve 2

Supply (Operating 

Pressure)

Port 2 
Port 1

Drain

Valve 1

Valve 2

Supply (Operating 

Pressure)

Port 2 

Port 1

Drain

(Plugged)

For Controlling

Two Valves Simultaneously

Note:  We recommend protecting Float Control tubing and valve from freezing temperatures.

CLA-VAL EUROPE

Chemin des Mésanges 1

CH-1032 Romanel/

Lausanne, Switzerland

Phone:   41-21-643-15-55

E-mail: [email protected]

CLA-VAL FRANCE

Porte du Grand Lyon 1

ZAC du Champ du Périer

France - 01700 Neyron

Phone: 33-4-72-25-92-93

E-mail: [email protected]

CLA-VAL

1701 Placentia Avenue 

 Costa Mesa, CA  92627

800-942-6326 

 

 Fax: 949-548-5441 

 

 Web Site: cla-val.com 

 

 E-mail: [email protected]

©

COPYRIGHT CLA-VAL 2019 Printed in USA  Specifications subject to change without notice. 

 

 

      

visit www.cla-val-latinamerica.com for Spanish literature

CLA-VAL CANADA

4687 Christie Drive

Beamsville, Ontario

Canada L0R 1B4

Phone:     905-563-4963

E-mail [email protected] 

CLA-VAL UK

Dainton House, Goods Station Road

Tunbridge Wells 

Kent TN1 2 DH England

Phone:   44-1892-514-400

E-mail: [email protected]

CLA-VAL PACIFIC

45 Kennaway Road

Woolston, Christchurch, 8023

New Zealand

Phone:  64-39644860

www.cla-valpacific.com

E-mail:  [email protected]

E-CF1-C1 (R-02/2019)

Отзывы: