CLA-VAL 100-01 Скачать руководство пользователя страница 2

INTRODUCTION

The Cla-Val 40-01/640-01 is an automatic valve designed to limit

the maximum flow rate regardless of changing line pressure.

It is hydraulically operated, pilot-controlled, diaphragm type

globe or angle valve. The pilot control is actuated by the

differential pressure produced across an orifice plate restriction

installed downstream of the valve. Accurate control is insured as

very small changes in the controlling differential produce

immediate corrective action of the main valve. Rate of flow is

adjustable by varying the spring loading on the pilot control.

INSTALLATION

1. Allow sufficient room around the valve to make adjustments

and for disassembly.

2. It is recommended that either gate or block valves be installed

on both ends of the Cla-Val Valve to facilitate isolating the valve

for preventive maintenance.

NOTE: BEFORE THE VALVE IS INSTALLED, PIPE LINES

SHOULD BE FLUSHED OF ALL CHIPS, SCALE, AND FOREIGN

MATTER.

3. Place valve in line with flow through the valve in the direction

indicated on the inlet plate or by flow arrows. Check all fittings

and hardware for proper makeup and that no apparent damage

is evident. Be sure main valve cover nuts/bolts are tight.

Pressure in some applications can be very high, be thorough in

checking and inspecting for proper installation and makeup.

4. For best control, it is recommended that the orifice plate

restriction be installed 1 to 5 pipe diameters downstream of the

main valve. The flow arrows should be pointing to the down-

stream side of the system.

5. A sensing line, supplied by other than Cla-Val, must be

connected between the orifice plate holder (4) and the

Differential Control (3). See dotted lines on schematic drawing.

6. Cla-Val Valves operate with maximum efficiency when mounted

in horizontal piping with the cover UP: however, other positions

are acceptable. Due to size and weight of cover and internal

components of six inch and larger valves, installation with the

cover up is advisable. This makes periodic inspection of internal

parts readily accessible.

OPERATING AND START-UP

1. Prior to pressurizing the valve assembly make sure the

necessary gauges to measure pressure in the system are

installed as required by the system engineer. A Cla-Val X101

Valve Position Indicator may be installed in the center cover port

to provide visual indication of the valve diaphragm assembly

position during startup.

CAUTION:

During startup and test procedures a large volume of

water may be discharged downstream. Check that the down-

stream venting is adequate to prevent damage to personnel and

equipment. All adjustments in pressure should be made slowly.

If the main valve closes too fast it may cause surging in upstream

piping.

2. With the downstream block valve closed, slowly open

upstream block valve. If isolation valves (B) are installed in the

pilot system, open these valves.(see schematic)

3. Carefully loosen the plug at top of cover assembly. If an

indicator (X101) is installed, loosen the bleed valve at top of

indicator. Bleed air from cover and tighten plug or bleed valve.

4. Carefully loosen tubing fittings at highest points and bleed air

from system. Retighten fittings.

NOTE: Be sure the sensing line, (dotted line shown on schemat-

ic) which connects the orifice plate holder (4) to the CDHS-18

Control (3) is installed. The 40-01/640-01 Rate of Flow Control

Valve will not function unless this sensing line is installed. Be sure

to bleed air from this sensing line at the CDHS-18 Control fitting.

5. Slowly open downstream block valve and adjust the CDHS-18

Control for required flow rate.Turn the adjustment screw clockwise

to increase flow rate and counterclockwise to decrease flow rate.

The adjustment screw should be turned slowly. A good procedure

is to make one adjustment turn with a pause to let the system

stabilize.

MAINTENANCE AND INSPECTION

1. Cla-Val Valves and Controls require no lubrication or packing

and a minimum of maintenance. However, a periodic inspection

schedule should be established to determine how the fluid

handled is affecting the operation of the valve assembly.

Minimum of once per year.

2.

Repair and maintenance procedures of the Hytrol Main Valve

and control components are included in a more detailed IOM

manual. It can be downloaded from our web site (www.cla-val.com)

or obtained by contacting a Cla-Val Regional Sales Office.

3. When ordering parts always refer to the catalog number

and stock number on the valve nameplate.

40-01/640-01

Rate of Flow Control Valve 

MODEL

INSTALLATION / OPERATION / MAINTENANCE

SYMPTOM

POSSIBLE CAUSE

Orifice plate assembly and/or
orifice sensing line clogged

Remove line and
clean orifice port
Clean or replace line

Readjust control

Adjustment below desired
set point
Control line shutoff valve to
cover or main outlet closed

Open shutoff valve

Adjustment above desired set
point

Readjust control

Pilot control diaphragm nut
loose or diaphragm leaks
(damaged)

Disassemble tighten
nut or replace
diaphragm

Clogged restriction assembly

Remove and clean 
or replace

Control line shutoff valve from
inlet to restriction closed

Open shutoff valve
and readjust

CV Flow control closed or
clogged

Disassembled and
clean

Pilot control disc worn or
nicked

Remove disc retainer
assembly and replace

Pilot valve stuck closed
Mineral deposits or foreign
matter under disc retainer
assembly

Remove plug and disc
retainer assembly
clean or replace

Main valve stuck closed
Mineral buildup on stem
Stem damaged 
Diaphragm leaks

Disassemble main
valve clean parts
and/or replace 
damaged parts

SOLUTIONS

Main valve
won’t open

Main valve
won’t close

Distributed By: M&M Control Service, Inc.

                http://www.mmcontrol.com/claval-index.php

800-876-0036     847-356-0566

Содержание 100-01

Страница 1: ...01 Distributed By M M Control Service INC Phone 800 876 0036 Fax 847 356 0747 Email Sales mmcontrol com Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847...

Страница 2: ...sed slowly open upstream block valve If isolation valves B are installed in the pilot system open these valves see schematic 3 Carefully loosen the plug at top of cover assembly If an indicator X101 i...

Страница 3: ...Strainer B CK2 Valve Isolation Valve C CV Flow Control Closing D Check Valves with Isolation Valve S CV Flow Control Opening Y X43 Y Strainer 3 2 D1 Y B1 1 A C B1 S B1 B2 4 OUTLET INLET D2 D3 X58C CDH...

Страница 4: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 5: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 6: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 7: ...tions are acceptable Due to size and weight of the cover and internal components of 8 inch and l arger valves installation with the cover UP is advisable This makes internal parts readily accessible f...

Страница 8: ...ng out probable causes and remedies the following three checks can be used to diagnose the nature of the problem before maintenance is started They must be done in the order shown Open Cocks Check ups...

Страница 9: ...d The stem should also be checked for scale build up See Maintenance section for procedure 11 For valves 6 and smaller the Hytrol Valve s freedom of move ment check can also be done after all pressure...

Страница 10: ...he nut and give it a sharp rap rather than a steady pull Usually several blows are sufficient to loosen the nut for further removal On the smaller valves the entire diaphragm assembly can be held by t...

Страница 11: ...mechanically restricting the stroke of the valve The cover must be removed the obstruc tion located and removed See Maintenance Section for procedure Inspection of Parts After the valve has been disa...

Страница 12: ...ex Nut 8 and larger 4 Stud 8 and larger 5 Cover Bearing 6 Cover 7 Stem Nut 8 Diaphragm Washer 9 Diaphragm 10 Spacer Washers 11 Disc Guide 12 Disc Retainer 13 Disc 14 Stem 15 Seat 16 Body 17 Spring 22...

Страница 13: ...a long life of dependable trouble free operation It s smooth flow passages and fully guided disc and diaphragm assembly assure optimum control when used in piping systems requiring remote control pres...

Страница 14: ...e Viton Rubber Parts suffix KB Optional diaphragm disc and o ring fabricated with Viton synthetic rubber Viton is well suited for use with mineral acids salt solutions chlorinated hydrocarbons and pet...

Страница 15: ...U S gpm or l s V Fluid Velocity feet per second or meters per second P Pressure Drop in psi or bar CV Factor Formulas for computing C Factor Flow Q and Pressure Drop V P CV Q P CV Q P CV Q P 2 V Funct...

Страница 16: ...arger valves installation with cover UP is advisable We recommend isolation valves be installed on inlet and outlet for maintenance Adequate space above and around the valve for service personnel shou...

Страница 17: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 18: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 19: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 20: ...e Screw 16 Cap Adj Screw PLS 12576 01D 6 MAX Adjusting screw turn clockwise to increase setting 3 8 NPT Inlet 1 3 4 max 3 16 9 2 10 13 1 8 NPT LOW PRESSURE CONNECTION 7 4 3 11 5 1 6 8 3 8 NPT OUTLET A...

Страница 21: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 22: ...evidence of cross threading Check inner and outer screens for clogging embedded foreign particles breaks cracks corrosion fatigue and other signs of damage CLEANING After inspection cleaning of the X...

Страница 23: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 24: ...Check spring for visible distortion cracks and breaks Inspect all parts for damage corrosion and cleanliness CLEANING After disassembly and inspection cleaning of the parts can begin Water service usu...

Страница 25: ...r Stamped on Side Description CV Flow Control Part Description Material ITEM DESCRIPTION QUAN 1 Cap SS only 1 2 Nut Jam 1 3 Seat 1 4 Gasket 1 5 Disc 1 6 Spring 1 7 Ring Retaining 1 8 Stem 1 9 O Ring 1...

Страница 26: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Страница 27: ...screen stock number 68373A All other parts available only in replacement assembly Standard 60 mesh pilot system strainer for fluid service PL X43 R 6 00 PARTS LIST Distributed By M M Control Service I...

Страница 28: ...of the inlet flange These two brass plates appear on 3 8 1 2 and 3 4 size valves and are located on the valve cover These two brass plates appear on 1 through 3 size screwed valves or 1 through 2 flan...

Страница 29: ...any of the foregoing or assume any additional liability or responsibility in connection with the product The liability of Cla Val is limited to material replacements F O B Newport Beach California TE...

Страница 30: ...01D 9817902B N A 9817903K 9817905E 9817905E 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 6 8 9169806J 9169807G 9169808E 9169809C 9169810A 9169817F 9169818D 9169819B 9169820K N A N A N A N A N A N A N A 91698...

Страница 31: ...Cl CFC2 C1 CSM 11 A2 2 CSM 11 A2 2 33A 1 33A 2 Pilot Assembly Only Complete Float Control less Ball Rod Disc Distributor Seals Mechanical Parts Assy Pilot Assembly Only Complete Internal Assembly Seal...

Отзывы: