STATUS:

Ready to Load

STATUS:

No LED/Lights lit

ACTION:

Check incoming voltage at Terminal

Block (TBI). Voltage should be between 11-16 volts.
Check the 1/4 amp inline fuse and make sure it
hasn’t blown. Replace monitor if fuse checks out 
as good.

STATUS:

Yellow power LED/Light  lit, but no

permit light

ACTION: 

Check Auxiliary (AUX) connections.

All three auxiliary lights must be on/lit to get a
permit light. If no auxiliary inputs are being used,
a jumper must be installed (see OTHER
COMPONENTS).

STATUS:

Solid red LED/Light on top sensor

ACTION:

Check compartment for wet sensor.

Remove sensor wire corresponding with LED.
Substitute with wire from nearest working sensor. 
If the LED remains lit, replace monitor. If the LED
corresponding to the substituted wire is lit, replace
the sensor or check wiring. 

STATUS:

Flashing red LED/Light in top sensor

ACTION:

Remove sensor wire corresponding with

the flashing LED. Substitute with a working sensor. 
If the same LED continues to flash, replace monitor. 
If flashing LED changes to the location of the sub-
stituted wire, check the wiring or replace the sensor.

STATUS:

Flashing red top sensor LED/Light in

compartment 6 on a 5 or less compartment trailer

ACTION: 

Check wiring at the terminator. If

connections are good, replace terminator.

STATUS:

All top red LED/Lights are flashing

ACTION:

Check common wire. Check for

low voltage at Terminal Block (TBI).

STATUS:

Solid red

LED/Light on bottom sensor. 

ACTION: 

Check

compartment for product. Hit
blue Retain/Reset Button to see
if condition clears. If condition
persists, repeat action from #4.

STATUS:

Flashing red LED/Light on

bottom sensor. 

ACTION: 

Check compartment for

product. Hit Retain/Reset Button to see if light
clears. Check wiring connections.