NOTE:

Some models are equipped with a dual ignition system.

The dual ignition system contains two direct spark

ignition modules in parallel.  Each module has its own

flame sense circuit and acts independently of the other.

If either bonnet limit thermostat opens because of high

heat or flame impingement, the entire ignition system

will shut down.

1. When a call for heat is received from the control supplying

24VAC to the ignition control module, the pre-purge delay

timer begins.  This delay time allows any air/sediment to be

ejected prior to burner ignition.  Following the pre-purge delay

period, the gas valve is energized and the spark ignitor sparks

for the trial ignition period.

2. When a flame is detected during the trial for ignition period, the

spark ignitor shuts off and the gas valve remains energized.

3. If no flame is detected by the flame sense circuit, the ignition

control module will go into safety lockout.  The valve will be

turned off immediately.  If the module has multiple retries and

no flame is detected, the gas valve is de-energized and the

module goes into an interpurge delay.  After this delay, the

module will attempt another trial for the ignition period.  This

will continue until the number of retries has been used up.  At

the time, the module will go into safety lockout.

4. Recovery from safety lockout requires one of the following:

a. A manual reset by opening and closing the loading door.

b. After one hour if the control thermostat is still calling for

heat, the module will automatically reset and the trial for

ignition period will start over.

5. Opening the loading door will cause the flame to extinguish.

Closing the door and starting the dryer will restart the trial for

ignition period.

6. Once the control thermostat has been satisfied and/or the

drying timer has been timed out, the ignition control

module(s) will be de-energized, the gas valve(s) will be de-

energized and the flames will extinguish.

7. The machine will continue to run in a cooldown mode without

heat.  This process will cool the load to the touch and help to

eliminate wrinkling.

Direct-Spark Ignition Operation

DIRECT  SPARK

IGNITION

OPERATION

Содержание HD30ST

Страница 1: ...30 lb STACK LAUNDRY DRYER Cissell Manufacturing Co 831 S First St P O Box 32270 Louisville Ky 40232 2270 Tel 502 587 1292 Fax 502 585 2333 Sales Fax 502 585 3625 Service Parts Fax 502 681 1275 THIS MA...

Страница 2: ...l occupants Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service mu...

Страница 3: ...apparell __ QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d apparell Ne touchez a aucun interrupteur Ne pas vous servir des telephones se trouvant dans le batiment ou vous vous tro...

Страница 4: ...s wrinkles from setting in and reduces the possibility of spontaneous combustion WARNING Be safe shut main electrical power and gas supply off externally before attempting service WARNING Never use dr...

Страница 5: ...tall to diagnose troubles to adjust remove or replace defective equipment or a part nor does it include any responsibility for transportation expense which is involved therein The warranty of Cissell...

Страница 6: ...Requirements 20 ExhaustandVenting 21 Rules for Safe Operation 22 OperatingInstructions CoinMeter 23 24 Service Savers 25 Troubleshooting 26 28 Spark Ignition System 29 30 General Maintenance 31 Baske...

Страница 7: ...n start demarrage Start arranquedeunmovimiento emission of heat in general mission de chaleur en general Warmeabgabeallgemein emisi n de calor cooling refroidissement Kuhlen enfriamiento dangerousvolt...

Страница 8: ...os dos sentidos directionofrotation sens de mouvement continu de rotation DrehbewegunginPfeilrichtung movimientogiratorioorotatorio en el sentido de la flecha End of Cycle caution attention Achtung at...

Страница 9: ...motors Installation clearance from all combustable material is 0 ceiling clearance for the first 4 102 mm from the front of the dryer After the first 4 102 mm the ceiling clearance required is 6 153...

Страница 10: ...Page 10 Outline Dimensions...

Страница 11: ...per hour per pocket 20 160 kcal h Natural or LP gases Gas Pressure 5 12 mbar 12 30 mbar WC input nat gas 3 5 8 7 mbar WC manifold press nat gas 11 27 4 mbar WC manifold press LP gas Gas Supply 1 2 NPT...

Страница 12: ...quire the care that your laundry dryers now provide At the end of the drying cycle a timed cool down control automatically takes over and continues the rotation of the fan and basket without heat unti...

Страница 13: ...necessary for the electrician to connect the power leads to the wire connectors within the service connection box on the rear of the dryer Do not change wiring without consulting factory as you may v...

Страница 14: ...gas pressure inlet supply to dryer 10 5 inches water column 26 2 mbar maximum Manifold pressure 3 5 inches water column 8 8 mbar pressure 6 L P gas only check the gas pressure inlet supply to dryer 13...

Страница 15: ...tem during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa The dryer must be isolated from the gas supply piping system by closing it s individual manual shutoff val...

Страница 16: ...nected upstream from the loop WARNING LIQUIFIEDPETROLEUMGASESONLY A gas pressure regulator for liquified petroleum gases is not furnished on the gas heated clothes dryers This regulator is normally fu...

Страница 17: ...300000 330000 350000 380000 400000 430000 450000 480000 504000 550000 605000 650000 705000 750000 806000 850000 907000 960000 1000000 3 4 3 4 3 4 3 4 3 4 3 4 1 1 1 1 1 4 1 1 4 1 1 2 1 1 2 1 1 2 2 2 2...

Страница 18: ...by a professional heating and air conditioner HVAC contractor Individual tumbler ducts should enter the main connector duct at a 45 angle in the direction of exhaust air flow The diameter of the main...

Страница 19: ...Enclosure plenum with service door This separates the dryer air from the room comfort air If dryers use room air instead of outside air additional heat loss can be another 25 Btu h 6 3 kcal h for each...

Страница 20: ...3716 HD20 1 20 9 1 450 765 6 153 87 561 HD30SL 30 13 6 600 1020 8 203 116 748 HD30 1 30 13 6 625 1063 8 203 120 774 HD50 1 50 22 7 850 1445 8 203 164 1058 HD75 1 75 34 1000 1700 8 203 192 1240 HD80 1...

Страница 21: ...e installing an elbow on energy saver models only 5 Do not install wire mesh or other restrictions in the exhaust duct 6 Use clean outs in the exhaust duct and clean periodically when needed Examine t...

Страница 22: ...warnings or precautions 7 Never tumble fiberglass materials in the dryer unless the labels say they are machine dryable Glass fibers break and can remain in the dryer and could cause skin irritation i...

Страница 23: ...perature heavy fabrics and hard to dry cottons and linens MEDIUM 150 F 66 C exhaust temperature permanent press synthetic blends LOW 135 F 58 C exhaust temperature delicate sheer fabrics 4 Press the S...

Страница 24: ...d for a capacity maximum load Overloading it will result in longer drying time and damp spots on some of the load Maximum operating efficiency depends on proper air flow The lint screen must be kept c...

Страница 25: ...arkignitionmodulediagnosticlight 5 Hasthebonnetthermostatorsafetythermostattripped If so push to reset CLOTHES ARE NOT SATISFACTORILY DRY 1 Timedcycle Didyouallowenoughheatingtimebeforethe cool downpa...

Страница 26: ...check with local power company for recommended corrective measures Check with local power company to insure that wiring is adequately sized for load Check all electrical connections and tighten any lo...

Страница 27: ...ccumulation or other causes that may prevent damper from opening Check duct work for lint build up Check installa tion sheet to insure that duct work and make up air openings are adequately sized Chec...

Страница 28: ...ory for correct size Make up air must be 4 to 6 times the exhaust area of the dryer Removelint Must be full open replace if not Adjust gas pressure per rating plate Check service section for recommend...

Страница 29: ...the module has multiple retries and no flame is detected the gas valve is de energized and the module goes into an interpurge delay After this delay the module will attempt another trial for the igni...

Страница 30: ...tch 1 D UnderBasketandBurnerHousingThermalSafetySwitches 2 E VariableThermostat 1 F PushtoStartSwitch 1 THERMOSTATCALLS FORHEAT IGNITION CYCLE BEGINS GASVALVE ON MAINBURNERFLAME DETECTED CONTROL LOCK...

Страница 31: ...e for 10 years normal service After that bearings and housing should be cleaned and repacked one third full with Chevron grease No SR1 2 See label on motor for further information If motor overheats c...

Страница 32: ...e1andFigure2 Checkthe two B pinsforequalclearance 3 Withthepinsinposition tightenthetwoNo 5boltsuntilflushagainstbackofdryer Retightencast ironbearingmountingboltsinthenumericalorderindicatedinFigure3...

Страница 33: ...g the sweep sheet C Mark this position and the nearest rib to this position D Remove the basket do not loosen the alignment bolts E With the basket on the floor spider up place one or two shims betwee...

Страница 34: ...shown hold switch mounting bracket firmly and adjust switch actuator D with needle nose pliers at E by twisting actuator right or left whichever is needed so that switch closes when end of air blade...

Страница 35: ...DEDASS Y 2 TUD0283 INSULATION TOP 3 TUD0375 COINCHUTE 4 TU7733 SCREW SELF TAP 5 TUD0258 SPRINGRETAINER 6 EA 00650 0 SWITCH LINTDRAWER 7 TUD0241 SWEEP SHEET LR TUD0239 SWEEP SHEET UR 8 TUD0240 SWEEP SH...

Страница 36: ...Page 36 FRONTPANELASSEMBLY See next page...

Страница 37: ...U7733 Screw 8 Self tapping 7 SB 00852 0 Washer star 8 CA 00699 0 Coin box bezel some models 9 ESA 00862 0 Reed switch 10 SB 00975 0 Screw 6 32 11 TUD0475WH Front panel Upper 12 SB 00836 0 Screw 10 pan...

Страница 38: ...ch pin 2 TU15536 Magnet read switch 3 MD 00360 0 Gasket door rim gasket 4 SB 00852 0 Washer 1 4 external starluck 5 SB 00921 0 Screw 1 4 20 round head 6 TU15073 Door hinge spacer 7 TU15076 Door rim w...

Страница 39: ...1 0 LOCK AND KEY CONTROL 2 CA 00748 0 TRIM BOTTOMALM 3 TUD0234WH COVER PLT W A 4 SB 00951 0 SCREW 8 5 TU2853 LINTDRAWERGASKET 6 TUD00366 MAGNETSNAPCATCH 7 TU7858 LABEL INSTRUCTIONS 8 CA 00749 0 TOP TR...

Страница 40: ...art No No Description 1 SB 00951 00 SCREW 8 2 TUD0547 MESHSCREEN 3 TUD0412 PLUG DOUBLE D NOLOCK 3A LA 00121 0 LOCK 4 TUD0544WH FRAME DRAWER 5 TUD0198 KICKPLATE 6 TUD0249WH COVERPLTW A 7 TU2853 GASKET...

Страница 41: ...ERMOSTAT ASSEMBLY Ref Part No No Description TUD0517 DMPTHERMOSTATCOMPLETEASSEMBLY 1 TUD0516 THERMOSTATBRACKET 2 EA 00411 0 SWITCH 220DEGREE 3 TU11991 THERMISTOR 4 TU3624 SCREW MACHINER H 6 32 5 TU340...

Страница 42: ...OSTAT Ref Part No No Description TUD0513 COMPLETE MCMTHERMOSTATASSEMBLY 1 TUD0259 BRACKET THERMOSTAT 2 EA 00606 0 THERMOSTAT 3 EA 00608 0 GROMMET RUBBER 4 EA 00411 0 SWITCH 220DEGREE 5 M262 SCREW 8 32...

Страница 43: ...ER TUD0506 COMPLETEASSEMBLY LOWER 1 M270 6LOCKWASHER 2 TU12253 STUD 6 32 3 TU14404 CONTROL DMP 4 TU14451 OVERLAY DMPCOIN UPPER TU14406 OVERLAY DMPCOIN LOWER 5 TU3400 NUT 6 32 6 TUD0336 COINDROP 25C 7...

Страница 44: ...UPPER TUD0510 COMPLETEASSEMBLY LOWER 1 TU12253 STUD 6 32 2 TU14404 DMPCONTROL 3 M270 6LOCKWASHER 4 TU3400 NUT 6 32 5 TU15185 OVERLAY DMPOPL UPPER TU15184 OVERLAY DMPOPL LOWER 6 TUD0458BLK LFTDMPPANEL...

Страница 45: ...6 COINMETER24V 25C F 10Minutes 2 EA 00619 0 SWITCH STARTSMALL 3 TUD0354 LABEL CNTRLROTARYLEFT UPPER TUD0355 LABLE CNTRLROTARYRIGHT LOWER 4 TUT316 LIGHT LED24VW 1 4Q C 5 TU4958 SCREW CARRIAGEBOLT 8 32X...

Страница 46: ...der Asm Galv 1 TUS15068 Stainless steel basket assy 1 TU15068 Galvanized basket assy 2 TU15087 Spider assy 3 SB 00965 0 Screw button cap 5 16 18 4 TU7006 Shim 5 VSB130 Washer cut 5 16 6 TU2814 5 16 Lo...

Страница 47: ...Page 47 Ref Part No No Description 1 TUD0083 JACKETWELDEDASS Y 2 TU7733 SCREW SELF TAP 3 TUD0246 BELTGUARDCOVER REAR VIEW...

Страница 48: ...No No Description TUD0532 COMPLETEPOWERBOXASSEMBLY 1 TUD0487 POWERBOX W A 2 TU7733 SCREW 8 32MACHINE 3 TU14985 RAIL DIN31 4 LG 4 TU15007 TERM BLKEND GRND 5 TU14958 TERMINALBLOCK 70A 600V 6 TU14959 TER...

Страница 49: ...1 4 20 Low head socket bolt 12 TU4787 3 8 16 hex nut 13 TU3243 3 8 Internal tooth washer 14 TU15686 10 32 x 3 4 lg Set screw One required for rotation sensor ONLY Ref No Part No Description 1 TU15173...

Страница 50: ...6 EA 00648 0 BRACKETCLIP 7 EA 00211 0 CONNECTOR3 8 STRT 8 DA 00510 0 PULLEY 2 5 50HZ DA 00516 0 PULLEY 2 60HZ 9 DA 00428 0 MOTOR1 2HP 115 230V 50 60 1PH DA 00447 0 MOTOR1 2HP 220 380V 50 230 460 60 1...

Страница 51: ...06 Sail switch assembly complete 1 F888 E Ring 2 TU1770 Insulator 3 TU1771 6 Tinnerman nut 4 TU2463 Actuator arm 5 TU3219 6 x 1 Round head screw 6 TU8155 Air switch 7 TU8171 Air switch bracket 8 TU347...

Страница 52: ...GPLATE 2 VSB130 5 16 WASHER 3 FB124 5 16 BOLT 4 TUD0171 BEARINGHOUSINGASS Y 5 DA 11711 0 SHAFT 6 TUD0187 KEY 7 TU14691 PULLEY2 5 8 TUD0197 AX60BELT 60cycle 9 TU15168 9 PULLEY 10 DA 00522 0 AX62BELT 50...

Страница 53: ...EW SELF TAP 2 GA 00765 0 SPARK MODULE 24V US TU14675 SPARK MODULE 24V AUST GA 11007 0 SPARK MODULE 24 CE 3 GA 00803 0 HI VOLTCABLE 4 TU2372 SNAP BUSHING 5 TU2490 PLUG 6 TU15138 TRANSFORMER 120V 200 24...

Страница 54: ...ECABLE 6 TU4934 NUT 1 4 20 7 TU2846 LOCK WASHER 1 4 8 TU2847 WASHER 1 4 9 CB36 HEX HD SCREW 1 4 20 10 TU3539 ORIFICE 11 GA 00774 0 PIPE MANIFOLD 12 TU14178 GASVALVENG TU14177 GASVALVELP 13 OP290 NIPPL...

Страница 55: ...Page 55...

Отзывы: