For

n

+1 redundancy, you can use one or two power sources for the two power supplies. For

n

+

n

redundancy,

you must use two power sources and connect each power supply to a separate power source.

Note

Some of the power supply modules have rating capabilities that exceed the fabric interconnect requirements.
When calculating your power requirements, use the fabric interconnect requirements to determine the amount
of power that is required for the power supplies.

Note

To minimize the possibility of circuit failure, make sure that each power-source circuit that is used by the
fabric interconnect is dedicated to the fabric interconnect.

For AC input application, please refer to the following statement:

Note

Statement 1005—

Circuit Breaker

This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the
protective devices are rated not greater than 20A (North America), 16A (Europe), and 13A (UK).

Warning

For the power cables to use with the power supplies, see

Power Cable Specifications

.

Note

Airflow Requirements

The fabric interconnect is positioned with its ports in either the front or the rear of the rack depending on your
cabling and maintenance requirements. You must have fan and power supply modules that move the coolant
air from the cold aisle to the hot aisle in one of the following ways:

• Port-side exhaust airflow—Cool air enters the chassis through the fan and power supply modules in the

cold aisle and exhausts through the port end of the chassis in the hot aisle.

You can identify the airflow direction of each fan and power supply module by its coloring. Blue or dark grey
coloring indicates port-side exhaust airflow.

To prevent the fabric interconnect from overheating and shutting down, you must position the air intake for
the fabric interconnect in a cold aisle. The fan and power supply modules must have the same direction of
airflow (even if their coloring is different). If you must change the airflow direction for the fabric interconnect,
you must shutdown the fabric interconnect before changing the modules.

Note

Preparing for Installation

4

Preparing for Installation

Airflow Requirements

Содержание UCS 6500 Series

Страница 1: ...an operating temperature of 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius If the fabric interconnect is not operating the temperature must be between 40 to 158 degrees Fahrenheit 40 to 70 degrees Celsius Humidity Requirements Buildings in which the climate is controlled by air conditioning in the warmer months and by heat during the colder months usually maintain an acceptable level of humi...

Страница 2: ...is type of interference can travel from the fabric interconnect to other devices through the power cable and power source or through the air as transmitted radio waves The Federal Communications Commission FCC publishes specific regulations to limit the amount of EMI and RFI that are emitted by computing equipment Each fabric interconnect meets these FCC regulations To reduce the possibility of EM...

Страница 3: ... chassis in a grounded rack the fabric interconnect is grounded because it has a metal to metal connection to the rack Alternatively you can ground the chassis by using a customer supplied grounding cable that meets your local and national installation requirements For U S installations we recommend 6 AWG wire Connect your grounding cable to the chassis with a grounding lug provided in the fabric ...

Страница 4: ...e power supplies see Power Cable Specifications Note Airflow Requirements The fabric interconnect is positioned with its ports in either the front or the rear of the rack depending on your cabling and maintenance requirements You must have fan and power supply modules that move the coolant air from the cold aisle to the hot aisle in one of the following ways Port side exhaust airflow Cool air ente...

Страница 5: ...ar mounting rails for proper mounting of the bottom support brackets or other mounting hardware Also you must have power receptacles that are located within reach of the power cords that are used with the fabric interconnect Statement 1048 Rack Stabilization The rack stabilizing mechanism must be in place or the rack must be bolted to the floor before installation or servicing Failure to stabilize...

Страница 6: ... equal to the depth of the chassis 7 Chassis width 17 3 in 43 9 cm 3 Width of the front clearance area equal to the width of the chassis with two rack mount brackets that are attached to it 19 0 in 43 3 cm 4 Both the front and rear of the chassis must be open to both aisles for airflow Note Preparing for Installation 6 Preparing for Installation Clearance Requirements ...