1-29
Cisco RF Gateway 10 Hardware Installation Guide
OL-16264-04
Chapter 1 Overview
Supported External AC-Input Power Shelf
Supported External AC-Input Power Shelf
The AC-input power shelf converts AC power from an external AC power supply source into DC power
that is suitable for powering on the Cisco RFGW-10.
The Lineage AC-DC power shelf is supported on the Cisco RFGW-10.
lists the Lineage power shelf specifications and the configurations supported on the
Cisco RFGW-10.
For information on installation, power shelf safety features, safety warnings, and troubleshooting the
Lineage power shelf, see the product documentation available at
Lineage AC-DC Power Shelf
The external Lineage AC-DC power shelf (part number J85480S1 L21) with AC module (CP2725TEZ
or CP2000AC54PE) is one-rack unit high (1.75 inch), and can be mounted on a standard 19-inch 4-post
equipment rack or telco-type rack. It is recommended that the Lineage power shelf is installed such that
the power connections face inside of the rack when viewed from the front. This allows the DC output
terminals of the external AC-input power shelf to be on the same side as the DC-input terminals of the
Cisco RFGW-10 chassis.
The Lineage AC-DC power shelf has two DC power sources, four AC-input power supply sources, and
J1 and J2 Jumper connectors. The J1 connector is used to connect a control interface cable and J2
connector is used for a shelf-to-shelf connection.
Note
Jumpers must be removed prior to inserting a connector into the J1 housing.
Table 1-14
Lineage Shelf Configurations Supported on Cisco RFGW-10
Component
Configuration 1
Configuration 2
No. of Lineage Shelves
(Part Number J85480S1 L21)
1
1.
For more information on ordering the Lineage kit, visit www.arrow.com
1
2
Maximum Output Power
11 KW
16 KW
Rectifiers Modules
4 CP2725TEZ
8 CP2725TEZ or
CP2000AC54
Power Output for Rectifiers
2725 W (maximum)
1200 W (maximum)
DC Power Output
–54 VDC
–54 VDC
AC Power Output
200–240 VAC
100–120 VAC
Operating Temperature
–40 C to 45 C
–5 C to 45 C
AC Power Cables
240 VAC AC power—4
120 VAC AC power—8
2
2.
The AC power cables supplied may vary with the country where the equipment is deployed.
DC Power Cables
Amphenol Y cables
•
Black—2
•
Red—2
Elmech straight cables
•
Black—4
•
Red—4