
7-13
Cisco ONS 15454 Procedure Guide, R5.0
December 2004
Chapter 7 Manage Alarms
NTP-A258 Provision External Alarms and Controls on the Alarm Interface Controller-International
•
Enabled
—
Check the check box to activate the fields for the alarm input number.
•
Alarm Type
—
Choose an alarm type from the drop-down list.
•
Severity
—
Choose a severity from the drop-down list.
The severity determines the alarm’s severity in the Alarms and History tabs and determines whether
the LEDs are activated. Critical (CR), Major (MJ), and Minor (MN) alarms activate the LEDs. Not
Alarmed (NA) and Not Reported (NR) do not activate LEDs, but do report the information in CTC.
•
Virtual Wire
—
Choose the virtual wire number from the drop-down list to assign the external device
to a virtual wire. Otherwise, do not change the None default. For information about the AIC-I virtual
wire, see the “Alarm Monitoring and Management” in the
Cisco ONS 15454 Reference Manual
.
•
Raised When—From the drop-down list, choose the contact condition (open or closed) that triggers
the alarm.
•
Description—A default description is provided; enter a different description if needed.
Step 10
To provision additional devices, complete
for each additional device.
Step 11
Click
Apply
.
Step 12
For external controls, click the
External Controls
tab and complete the following fields for each control
wired to the ONS 15454 backplane:
•
Enabled
—
Check this check box to activate the fields for the alarm input number.
•
Control Type—Choose the control type from the drop-down list: air conditioner, engine, fan,
generator, heat, light, sprinkler, or miscellaneous.
•
Trigger Type
—
Choose a trigger type: a local Minor, Major, or Critical alarm; a remote Minor, Major,
or Critical alarm; or a virtual wire activation.
•
Description
—
Enter a description.
Step 13
To provision additional external controls, complete
for each device.
Step 14
Click
Apply
.
Note
When you provision an external alarm, the alarm object is ENV-IN-
nn
. The variable
nn
refers to
the external alarm’s number, regardless of the name you assign.
Note
Environmental alarms that you create (and name) should be recorded locally for the NE. Both
the Alarm name and resolution are node-specific.
Stop. You have completed this procedure.
Содержание ONS 15454 Series
Страница 28: ...Tables xxviii Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Страница 44: ...Tasks xliv Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Страница 53: ...liii Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Страница 55: ...lv Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Страница 126: ...4 14 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 4 Turn Up Node NTP A256 Set Up SNMP ...
Страница 168: ...5 42 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 5 Turn Up Network NTP A172 Create a Logical Network Map ...
Страница 304: ...10 8 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 10 Change Node Settings NTP A87 Change SNMP Settings ...
Страница 410: ...16 4 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 16 Power Down the Node NTP A114 Power Down the Node ...
Страница 510: ...17 100 Cisco ONS 15454 Procedure Guide R5 0 March 2005 Chapter 17 DLPs A1 to A99 DLP A99 Determine Available VLANs ...
Страница 746: ...20 102 Cisco ONS 15454 Procedure Guide R5 0 March 2005 Chapter 20 DLPs A300 to A399 DLP A399 Install a UBIC H EIA ...
Страница 828: ...A 14 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 850: ...Index IN 22 Cisco ONS 15454 Procedure Guide R5 0 December 2004 description 4 11 remove 18 23 ...