2-9
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 2 Install Cards and Fiber-Optic Cable
NTP- D16 Install STM-N Cards and Connectors
Refer to the card’s reference section in the “Optical Cards” chapter of the
Cisco ONS 15454 SDH
Reference Manual
for more information about slot and bandwidth restrictions.
Step 2
Open the card latches/ejectors.
Step 3
Use the latches/ejectors to firmly slide the optical card along the guide rails until the card plugs into the
receptacle at the back of the slot.
Step 4
Verify that the card is inserted correctly and close the latches/ejectors on the card.
Note
It is possible to close the latches/ejectors when the card is not completely plugged into the
backplane. Ensure that you cannot insert the card any further.
Note
If you install the wrong card in a slot, complete the
“NTP-D227 Remove and Replace a Card”
Step 5
Verify the LED activity:
•
The red FAIL LED turns on for 20 to 30 seconds.
•
The red FAIL LED blinks for 35 to 45 seconds.
•
All LEDs blink once and turn off for 5 to 10 seconds.
•
The ACT or ACT/STBY LED turns on. The signal fail (SF) LED can persist until all card ports
connect to their far-end counterparts and a signal is present.
Note
The booting STM-N card will send an AIS-L to the far-end receiver as long as it is
Locked-enabled, disabled.
Step 6
If the card does not boot up properly, or the LED activity does not mimic
, check the following:
•
When a physical card type does not match the type of card provisioned for that slot in CTC, the card
might not boot. If an optical card does not boot, open CTC and verify that the slot is not provisioned
for a different card type before assuming the card is faulty.
•
If the red FAIL LED does not turn on, check the power.
•
If you insert a card into a slot provisioned for a different card, all LEDs turn off.
•
If the red FAIL LED is illuminated continuously or the LEDs behave erratically, the card is not
installed properly. Remove the card and repeat Steps
to
Table 2-3
Maximum Bandwidth by Shelf Slot for the MRC-12 in Different Cross-Connect
Configurations
XC Card Type
Maximum Bandwidth in Slots 1
through 4 and 12 through 17
Maximum Bandwidth
in Slots 5, 6, 12, or 13
XC-VXL-2.5G
OC-48
OC-48
XC-VXC-10G/XC-VXL-10G
OC-48
OC-192
Содержание ONS 15454 SDH
Страница 26: ...Tables vi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 ...
Страница 62: ...xxii Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 64: ...xxiv Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 66: ...xxvi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 414: ...16 4 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Chapter 16 Power Down the Node NTP D114 Power Down the Node ...
Страница 832: ...A 14 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 860: ...Index IN 28 Cisco ONS 15454 SDH Procedure Guide R6 0 78 17194 01 ...