Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 9 Manage Alarms
NTP- D247 Provision External Alarms and Controls on the Alarm Interface Controller–International
Step 11
If you are provisioning external controls, click the
External Controls
tab and complete the following
fields for each external control wired to the ONS 15454 SDH connectors:
•
Enabled
—
Check this check box to activate the fields for the alarm input number.
•
Control Type—Choose the control type from the drop-down list: air conditioner, engine, fan,
generator, heat, light, sprinkler, or miscellaneous.
•
Trigger Type
—
Choose a trigger type: a local minor, major, or critical alarm; a remote minor, major,
or critical alarm; or a virtual wire activation.
•
Description
—
Enter a description.
Step 12
To provision the other external controls, complete
for each additional device.
Step 13
Click
Apply
.
Note
When you provision an external alarm, the alarm object is ENV-IN-
nn
. The variable
nn
refers to
the external alarm’s number, regardless of the name you assign.
Note
Environmental alarms that you create (and name) should be recorded locally for the network
element (NE). Both the alarm name and resolution are node-specific.
Stop. You have completed this procedure.
Содержание ONS 15454 SDH
Страница 26: ...Tables vi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 ...
Страница 62: ...xxii Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 64: ...xxiv Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 66: ...xxvi Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 About this Guide ...
Страница 414: ...16 4 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Chapter 16 Power Down the Node NTP D114 Power Down the Node ...
Страница 832: ...A 14 Cisco ONS 15454 SDH Procedure Guide R7 0 78 17194 01 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 860: ...Index IN 28 Cisco ONS 15454 SDH Procedure Guide R6 0 78 17194 01 ...