Chapter 1 Install the Shelf and Common Control Cards
NTP- G10 Attach Wires to Alarm, Timing, LAN, and Craft Pin Connections
Step 6
Continue with the
“NTP-G10 Attach Wires to Alarm, Timing, LAN, and Craft Pin Connections”
Stop. You have completed this procedure.
NTP-G10 Attach Wires to Alarm, Timing, LAN, and Craft Pin
Connections
Caution
Always use the supplied ESD wristband when working with a powered ONS 15454 ETSI. Plug the
wristband cable into the ESD jack located on the lower-right outside edge of the shelf assembly.
Table 1-2
Pin Assignments for the AEP
AEP Cable Wire
Backplane Pin
AIC-I Signal
AEP Signal
Black
A1
GND
AEP_GND
White
A2
AE_+5
AEP_+5
Slate
A3
VBAT–
VBAT–
Violet
A4
VB+
VB+
Blue
A5
AE_CLK_P
AE_CLK_P
Green
A6
AE_CLK_N
AE_CLK_N
Yellow
A7
AE_DIN_P
AE_DOUT_P
Orange
A8
AE_DIN_N
AE_DOUT_N
Red
A9
AE_DOUT_P
AE_DIN_P
Brown
A10
AE_DOUT_N
AE_DIN_N
Purpose
This procedure installs alarm, timing, LAN, and craft wires on the
ONS 15454 shelf. These wires are attached to the mechanical interface card
(MIC) FMECs on the ETSI shelf and are attached to the backplane on the
ANSI shelf.
Tools/Equipment
Connectors according to function
Twisted #22 or #24 AWG (0.51 mm² or 0.64 mm²) shielded wires for LAN
or craft
75-ohm coaxial cable with 1.0/2.3 miniature coax connector
0.51 mm² or 0.64 mm² (#22 or #24 AWG) alarm wires
Prerequisite Procedures
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only), page
1-30
NTP-G5 Remove the Backplane Covers (ANSI Only), page 1-28
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None