Figure 1: Rack Specification
Mounting Flange
Dimension Z
Rack Mounting Hole
Center-Center Y
Rack Front Opening X
Rack Type
482.6mm (19")
465mm (18.312")
450.8mm (17.75")
ANSI 19" racks
584.2mm (23")
566.7mm (22.312")
552.45mm (21.75")
ANSI 23" racks
533.4mm(21")
515.0mm(20.276")
500.0mm(19.68")
ETSI 21" racks
Ground Description
The NCS 1000 32-channel mux/demux patch panels have two grounding options on the left and right rear
side. You can choose from the two grounding options to ground the patch panels. The rear side of the patch
panels, adapter brackets, the straight adapter brackets, and the Z-shaped adapter brackets are unpainted and
treated with conductive finishing. The grounding lug has provisions for connecting a minimum ground cable
of 14 AWG.
Ground Connection Warnings
Take note of the following ground connection warnings:
The appliance must be connected to a grounded outlet.
Apparatets stikprop skal tilsluttes en stikkontakt med jord, som giver forbindelse til stikproppens jord.
Laite on liitettävä suojakoskettimilla varustettuun pistorasiaan.
Apparatet må tilkoples jordet stikkontakt.
Apparaten skall anslutas till jordat uttag.
Statement 414.
Warning
Install Cisco NCS 1000 32-Channel Mux/Demux Patch Panel
2
Install Cisco NCS 1000 32-Channel Mux/Demux Patch Panel
Ground Description