C H A P T E R
3
Cabinet and Rack Installation
•
Cabinet and Rack Requirements, on page 13
Cabinet and Rack Requirements
This section provides the Cisco MDS 9000 Series switches requirements for the following types of cabinets
and racks in an external ambient air temperature range of 0 to 40°C. If you are selecting an enclosed cabinet,
we recommend that you choose one of these thermally validated types:
• Standard perforated cabinets
• Solid-walled cabinets with a roof fan tray (bottom-to-top cooling)
General Requirements for Cabinets and Racks
A cabinet or rack must belong to one of the following types:
• Standard 19-in. four-post EIA cabinet or rack, with mounting posts that conform to English universal
hole spacing per section 1 of ANSI/EIA-310-D-1992. See
Requirements Specific to Perforated Cabinets
and
Requirements Specific to Solid-Walled Cabinets
.
• Standard two-post telco rack, with mounting posts that conform to English universal hole spacing per
section 1 of ANSI/EIA-310-D-1992.
The cabinet or rack must also meet the following requirements:
• The minimum vertical rack space per chassis should be 1 RU, equal to 1.75 in. (4.4 cm).
• The width between the inside edges of the mounting posts must be at least 17.75 in. (45.1 cm). This is
the distance between the two front posts of the four-post EIA racks.
• The minimum rack-load ratings per RU are listed in the following table:
Rack Type
7.5 lb (3.4 kg)
EIA (4 post)
15 lb (6.8 kg)
Telco (2 post)
Cisco MDS 9148V-K9 Switch Hardware Installation Guide
13