Catalyst 4500 Series Switch, Cisco IOS Software Configuration Guide - Cisco IOS XE 3.9.xE and IOS 15.2(5)Ex
Chapter 14 Environmental Monitoring and Power Management
Power Management
illustrates how the 6000 W AC power supply is evaluated in redundant mode.
In combined mode, all the inputs to the chassis must be at the same voltage.
illustrates how the 6000 W AC power supply is evaluated in combined mode.
Table 14-7
Output Power in Conbined Mode for the 4200 W AC Power Supply
Power Supply
12 V (data) (W)
-50 V (PoE) (W)
Total Power (W)
1
1.
Power supply outputs’ drawing should not exceed the total power.
Both sides at 110 V AC
1188
1531
1700
Both sides at 110 V AC + 110 V AC
2448
3071
3570
One side at 110 V AC + 110 V AC, the
other at 110 V AC
1818
2301
2660
Both sides at 220 V AC
2448
3071
3570
Both sides at 220 V AC + 220 V AC
2448
6142
7070
Both sides at 220 V AC + 220 V AC, the
other at 220 V AC
2447
4607
5320
Table 14-8
Output Power in Redundant Mode for the 6000 W AC Power Supply
Power Supply
12 V (data)
(W)
-50V (PoE)
(W)
Total
Power
(W)
1
1.
Power supply outputs’ drawing should not exceed the total power.
110 V AC
850
922
1050
110 V AC + 110 V AC
1700
1850
2100
220 V AC
2200
2400
3000
220 V AC + 220 V AC
2200
4800
6000
Table 14-9
Combined Mode Output for the 6000 W AC Power Supply
Power Supply
12 V (data) (W)
-50 V (PoE) (W) Total Power (W)
1
1.
Power supply outputs’ drawing should not exceed the total power.
Both sides at 110 V AC
1530
1531
1710
Both sides at 110 V AC + 110 V AC
3060
3071
3590
One side at 110 V AC + 110 V AC, the
other at 110 V AC
2295
2301
2680
Both sides at 220 V AC
3960
3984
5140
Both sides at 220 V AC + 220 V AC
3960
7968
10170
Both sides at 220 V AC + 220 V AC,
the other at 220 V AC
2970
5976
7610