This chapter explains how to install an IPX 8/16/32.

Site Preparation

The IPX 8/16/32 site must meet the following requirements:

Space
Each IPX 16/32 cabinet requires a floor space of 22 inches (55.9 cm) wide and 80 inches
(203.2 cm) deep. Each IPX 8 cabinet requires a floor space 19 inches (48.25 cm) wide and
24 inches (61.0 cm) deep. This depth measurement allows for opening the front and back cabinet
doors. Sufficient clearance around the cabinet is also necessary to allow access to the front and
back of the cabinet while the doors are open.

Power
An AC or DC power source must be available within six feet of the IPX 16/32 cabinet. At 180 to
264 VAC, an IPX 16 may require up to 9.2 A maximum (1700 VA) and an IPX 32 up to 17 A
maximum (3100 VA). At –42 to -56 VDC, an IPX 16 may require up to 28 A maximum (1200
W) and an IPX 32 up to 50 A maximum (2100 W).

Cooling
The site must be capable of maintaining an ambient temperature of 40˚C (max.) while the system
is operating (recommended range is 20˚C to 30˚C). Each fully loaded IPX 8 node dissipates
approximately 1300 BTUs (0.38 KW hour) to the room; the IPX 16 cabinet, 3419 BTUs (1 KW
hour), and the IPX 32 cabinet, 6836 BTUs (2 KW hour).

Weight
Each fully loaded IPX 32 cabinet can weigh up to 700 lbs (318 kgs). A fully loaded IPX 16
cabinet can weigh up to 400 lbs (182 kgs). Each fully loaded IPX 8 cabinet can weigh up to
125 lbs. (55 kgs).

Flooring
Raised flooring with sufficient under-floor space to house the cables is recommended.

Mounting
The IPX 8 cabinet can be mounted in a rack or be left free-standing. The location of the IPX
should give consideration to the routing of the data cables and the termination of the telephone
company or common carrier circuits.

Содержание BPX 8600 Series

Страница 1: ... A maximum 3100 VA At 42 to 56 VDC an IPX 16 may require up to 28 A maximum 1200 W and an IPX 32 up to 50 A maximum 2100 W Cooling The site must be capable of maintaining an ambient temperature of 40 C max while the system is operating recommended range is 20 C to 30 C Each fully loaded IPX 8 node dissipates approximately 1300 BTUs 0 38 KW hour to the room the IPX 16 cabinet 3419 BTUs 1 KW hour an...

Страница 2: ...four sets of holes two sets at the lower front and two sets at the lower rear Each set consists of a large socket access hole above a smaller hole The lower smaller hole accepts the bolt that is attached to the floor The upper larger hole provides access for a socket wrench to tighten the bolt see Figure 2 1 and Figure 2 2 Figure 2 1 Bolting the IPX16 32 to the Floor Rear View of Cabinet H8097 Bol...

Страница 3: ...wing tools and equipment are required to install the IPX Flat blade screwdriver set Phillips screwdriver set Grounding wrist strap DVM digital voltmeter Wrench 1 for raising and lowering cabinet feet H8098 6 80 17 27cm 8 40 21 37cm 1 00 2 54cm 24 45 62 10cm Cable entry cutout Cabinet rear 3 8 hole 7 8 access hole 4 places ...

Страница 4: ...of the slots in the top surface of the cabinet Figure 2 3 and Figure 2 4 Figure 2 3 Top Mounting Bracket Step 2 Rotate the top mounting bracket towards the second cabinet so that the flange at the other end of the top mounting bracket fits into the slot on the top surface of the second cabinet Figure 2 4 Step 3 Secure the mounting bracket by inserting the provided screw into the elongated hole in ...

Страница 5: ...nting bracket towards the second cabinet so that the straight recess slides around the screw in the second cabinet Figure 2 6 Step 4 Tighten the lock nuts to secure the mounting bracket in place Figure 2 7 Step 5 Perform this procedure for both the front and the rear of the cabinet Figure 2 5 Bottom Mounting Bracket IPX 16 32 Top mounting bracket Securing screw IPX cabinet 1 IPX cabinet 2 H8100 IP...

Страница 6: ...Figure 2 6 Positioning the Bottom Mounting Bracket IPX 16 32 Figure 2 7 IPX 16 32 Cabinets Joined at the Bottom Initial position Final position Screws supporting cabinet foot H8102 IPX cabinet 1 IPX cabinet 2 Mounting bracket Lock nut Lock nut Cabinet feet Floor H8103 ...

Страница 7: ...ing hardware it comes with two rack mounting rails strapped to the top packing plate To install the IPX 8 in a rack by using these rails refer to Figure 2 8 and proceed as follows Step 1 Remove the rack mounting rails from the packaging along with the package of mounting hardware Step 2 Locate the tapped holes on the side of the IPX 8 cabinet One set of holes is for front mounting of the cabinet t...

Страница 8: ...nual IPX 8 Cabinet Installation Figure 2 8 Installing Rack Mounting Kit 6027A Power Supply AC Logic Failed Active 6027A Power Supply AC Logic Failed Active IPX8 Screw H8104 Rack mount rail Front mount Center mount Rear mount ...

Отзывы: