C H A P T E R
7
Removing and Replacing FRUs
This chapter describes procedures for removing and replacing field-replaceable units (FRUs) from Cisco
ASR 1001-HX and 1002-HX Routers.
•
Removing and Replacing the Power Supplies, page 111
•
Removing and Replacing USB Flash Memory Stick, page 117
•
Removing and Replacing a DIMM, page 117
•
Removing and Replacing an EPA, page 128
•
Removing and Replacing Fans, page 131
•
Installing the Crypto Module, page 140
•
Repacking the Router, page 144
Removing and Replacing the Power Supplies
The following sections describes the procedures for removing and replacing the Cisco ASR 1001-HX Router
and Cisco ASR 1002-HX Router power supplies.
The Cisco ASR 1001-HX Router and Cisco ASR 1002-HX Router have redundant power supplies that
can be hot-swapped.
Note
The Cisco ASR 1001-HX Router has two power supply slots that are accessed from the rear of the chassis:
power supply slot 0 (PS0) and power supply slot 1 (PS1) are on the left of the chassis power switch.
The Cisco ASR 1002-HX Router has two power supply slots that are accessed from the front of the chassis:
power supply slot 0 (PS0) is on the bottom; and power supply slot 1 (PS1) is on the top (next to the chassis
power switch). The removal and installation procedures are the same for both routers.
Note
Cisco ASR 1001-HX Router and Cisco ASR 1002-HX Router Hardware Installation Guide
111