10.- MAINTENANCE
The
SVGm
static generator requires minimum preventive maintenance.
It is recommended to follow the notes described in this chapter to avoid premature
damage to the device's components.
shows the maintenance jobs with their respective time intervals.
Table 35: Static generator maintenance�
Description
Interval
Standard maintenance
12 months
Replacement of the cooling fans
40000 h
SVGm-3WF-xxxC-690 and SVGm-4WF-xxxC-550:
Surge protective devices maintenance
12 months and after
adverse weather events
The device controls the maintenance intervals and shows the
symbol on the main screen of the
device if maintenance is required.
The warnings screen, “
” describes the type of maintenance procedures that must be
carried out.
Note:
The time intervals of the maintenance operations can vary depending on the device’s operating
conditions and environmental factors.
Follow the safety instructions in the
section before carrying out
any maintenance on the
SVGm
.
Failure to follow these instructions may result in injury or even death�
Certain components in the device can reach high temperatures� Allow the device to
cool down before performing any maintenance operations�
10�1�- STANDARD MAINTENANCE
Perform maintenance every 6 to 12 months, depending on the level of environmental
dirt and operation of the device.
The device will indicate that the maintenance procedures must be carried out every 12
months.
For an installation with devices in parallel, standard maintenance must be performed on
all devices at the same time.
Содержание SVGm-3WF-100C-480
Страница 1: ...SVGm M248B01 03 21A Static var generator INSTRUCTION MANUAL ...
Страница 2: ...2 SVGm Instruction Manual ...
Страница 98: ...98 SVGm Instruction Manual 14 CE CERTIFICATE ...
Страница 99: ...99 Instruction Manual SVGm ...
Страница 100: ...100 SVGm Instruction Manual ...
Страница 101: ...101 Instruction Manual SVGm ...