17
Instruction Manual
RGU-10 B, RGU-10 B RCM
If the device trips through any event, the screen’s background changes to
red
and the reason for the
trip is displayed.
Figure 9: Display RGU-10B�
Display messages by device trip,
.
Table 6: Display messages by device trip�
Message
Cause of trip
TESt
Test
EXT
Remote signa
l
ON/OFF
ALAR
Trip of a leakage current
Other display messages,
Table 7: Other display messages�
Message
Description
SAVE
Validate configuration values
EXIT
Exits programming mode
ERRt
Poor toroid connection
OVR
Current leakage reading off scale
4�6�- OPERATION
When the device is powered at its rated voltage, the green LED
ON
the front is on, the backlit LCD is
green indicating the software and hardware version. After a short while, the version disappears and
the default display values appear on the display.
Figure 10:Initial screens�
The display shows the delay and sensitivity settings as well as the instant leakage current reading.
While the device is operating, the display shows the following symbols while the device is being pro-
grammed and set,
.
Содержание RGU-10 B RCM
Страница 1: ...INSTRUCTION MANUAL Residual current device and monitor RGU 10 B RGU 10 B RCM M087B01 03 20A...
Страница 2: ...2 RGU 10 B RGU 10 B RCM Instruction Manual...
Страница 27: ...27 Instruction Manual RGU 10 B RGU 10 B RCM 9 CE CERTIFICATE...
Страница 28: ...28 RGU 10 B RGU 10 B RCM Instruction Manual...
Страница 29: ...29 Instruction Manual RGU 10 B RGU 10 B RCM...
Страница 30: ...30 RGU 10 B RGU 10 B RCM Instruction Manual...
Страница 31: ...31 Instruction Manual RGU 10 B RGU 10 B RCM...
Страница 32: ...32 RGU 10 B RGU 10 B RCM Instruction Manual...
Страница 33: ...33 Instruction Manual RGU 10 B RGU 10 B RCM...