1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the device:
a) The device meets the specifications described in your order.
b) The device has not suffered any damage during transport.
c) Perform an external visual inspection of the device prior to switching it on.
d) Check that it has been delivered with the following:
- Installation guide
If any problem is noticed upon reception, immediately contact the transport
company and/or
CIRCUTOR’s
after-sales service.
2�- PRODUCT DESCRIPTION
REC4
is a 2 or 4-pole type A RCCB linked to a smart reclosing mo tor, which enables safe
reclosing of the corresponding RCCB.
In the
REC4-2P
model, the insulation reclosing mode is used for high sensitivity protection, so
that the device only recloses when the fault that caused tripping has disappeared. The rest of
the models imple ment the timed reclosing mode to ensure power supply continuity.
The device features:
-
2 LED
indication.
- Automatic reclosing by insulation or Time, depending on the model (
).
-
Protection cover
for the reclosing system.
-
Mode selection
switch
to select between Manual and Automatic operating mode and
physically lock the reclosing device.
Table 3: REC4 Models�
Models
Reclosure mode
Rated current (In)
Sensitivity (
Δ
In)
REC4-2P-40-30
Isolation
40 A
30 mA
REC4-2P-63-30
Isolation
63 A
30 mA
REC4-2P-40-300
Time
40 A
300 mA
REC4-2P-63-300
Time
63 A
300 mA
REC4-4P-40-30
Time
40 A
30 mA
REC4-4P-63-30
Time
63 A
30 mA
REC4-4P-40-300
Time
40 A
300 mA
REC4-4P-63-300
Time
63 A
300 mA
6
REC4
Instruction Manual
Содержание REC 4
Страница 1: ...INSTRUCTION MANUAL M202B01 03 20A RCCB with automatic reclosing device REC 4...
Страница 2: ...2 REC4 Instruction Manual...
Страница 18: ...81 91 5 35 5 101 55 87 5 45 76 Figure 12 REC4 4P dimensions 18 REC4 Instruction Manual...
Страница 20: ...9 CE CERTIFICATE 20 REC4 Instruction Manual...
Страница 21: ...21 Instruction Manual REC4...
Страница 22: ...22 REC4 Instruction Manual...
Страница 23: ...23 Instruction Manual REC4...