101
Instruction Manual
line-M
13�6�4�- CONFIGURATION WEBSITE
To access the internal configuration website, the device’s IP address has to be entered into the browser
address bar. The
line-LM40I-TCP kit
is set by default to DHCP mode.
The IP address can be obtained via Bluetooth® using the
MyConfig
application. The device can be
identified by its MAC address using software such as
Advanced IP Scanner or IP Setup Program
.
“10.4.4.- CONFIGURATION WEBSITE”
13�6�5�- MOBILE APP
The
MyConfig
mobile app, which can be used to set up Wi-Fi and Ethernet communications via
Bluetooth®, can be downloaded free of charge from Google Play (Android).
13�7�- TECHNICAL FEATURES: line-LM40I-TCP kit
AC Power supply
Rated voltage
80 ... 264 V~
Frequency
50 ... 60 Hz
Consumption
10.5 ... 14.5 VA
Installation category
CAT III 300V
DC Power supply
Rated voltage
100 ... 300 V
Consumption
9 ... 9.5 W
Installation category
CAT III 300V
Digital inputs
Quantity
40
Type
Optocoupler
Insulation
4.2 kV
Input impedance
1.4 kΩ
Consumption
60 mA inputs OFF
240 mA inputs ON
RS-485 interface
Bus
RS-485
Baud rate
4800 - 9600 - 19200 - 38400 - 57600 - 115200 bps
Data bits
7 - 8
Stop bits
1 - 2
Parity
without - even - odd
RS-232 interface
Bus
RS-232
Baud rate
4800 - 9600 - 19200 - 38400 - 57600 - 115200 bps
Data bits
7 - 8
Stop bits
1 - 2
Parity
without - even - odd
Содержание line-LM20I-TCP kit
Страница 1: ...INSTRUCTION MANUAL Expansion modules for the line CVM and line EDS devices M239B01 03 20B...
Страница 2: ...2 line M Instruction Manual...
Страница 95: ...95 Instruction Manual line M 118 105 45 35 7 90 44 70 Figure 47 line LM20I TCP kit dimensions...
Страница 103: ...103 Instruction Manual line M 118 157 5 45 35 7 90 44 70 Figure 52 line LM40I TCP kit dimensions...
Страница 105: ...105 Instruction Manual line M 16 CE CERTIFICATE...
Страница 106: ...106 line M Instruction Manual...
Страница 107: ...107 Instruction Manual line M...