91
Instruction Manual
line-CVM-D32
7�3�9�- DIGITAL OUTPUTS
Function 0x02
is used for these variables.
Table 27: Modbus Memory Map: Digital output status�
Parameter
Format
Address
Value
Digital Output 1 status
bool
7539
0:
Deactivated
1:
Activated
Digital Output 2 status
bool
754D
0:
Deactivated
1:
Activated
Function 0x04
is used for these variables.
Table 28: Modbus Memory Map: Alarms�
Parameter
Format
Address
Units
Digital Output 1 alarm activation date
Uint [32]
7537-7538
Seconds
Digital Output 2 alarm activation date
Uint [32]
754B-754C
Seconds
7�3�10�- DEVICE CONFIGURATION VARIABLES
The following functions are used for these variables:
Function 0x03
: register readout.
Function 0x10
: Writing multiple registers.
7�3�10�1�- Measurement Configuration
Table 29: Modbus Memory Map: Measurement configuration�
Measurement configuration
Configuration variable
Format
Address
Valid data range
Default value
Primary voltage
Float [32]
2710-2711
1.0 ... 2000000.0 V
-
Secondary voltage
Float [32]
2712-2713
1.0 ... 2000000.0 V
-
Primary current
Float [32]
2714-2715
1.0 ... 2000000.0 A
-
Secondary current
Float [32]
2716-2717
0.25 ... 5.00 A
-
Quadrants
Uint [16]
2722
2:
2Q -
4:
4Q
4
Measurement convention
Uint [16]
1388
0:
IEC -
1:
IEEE -
2:
Circutor
0
Installation type
Uint [16]
2A9D
0:
2W-1Ph -
1:
2W-2Ph -
2:
3W-2Ph -
3:
3W-3Ph -
4:
4W-3Ph -
5:
ARON
4
Aggregation period
(13)
Uint [16]
2ACB
60... 3600 s
600 s
Maximum demand integration
period
Uint [16]
274C
60... 3600 s
900 s
Maximum demand calculation
type
(14)
Uint [16]
274D
0:
Sliding window
1:
Fixed
0
Currency
String
27FC-27FD
EUR
Display backlight
Uint [16]
280D
1... 99 min
15 min
Password
Uint [32]
2A97-2A98
00000... 99999
97531
Current tariff
(14)
Uint [16]
59DC
1:
Tariff 1 -
2:
Tariff 2 -
3:
Tariff 3 -
4:
Tariff 4
1
Harmonics display
(15)
Bool
1782
0
: Not displayed
FF00
: Display
0
(13)
The programmed value must be divisible by 60, i.e. the
3660 / Aggregation period division
must be exact. It must also