13
Instructions Manual
GETEST
4�2�- DESCRIPTION OF THE Getest APP
The
Getest
application
consists of 2 screens: a Control screen to programme the device and another
screen for Results. A description of the control screen is shown in
Device Identifier
Mains frequency
Wireless connection
button
Test current to be injected
Type of test
Resistance
Maximum defect
current
Button to start the
sequence
Button to cancel the
sequence
Adjustment
Control screen
Results screen
Figure 4: Control screen description�
4�3�- START-UP
1�-
Connect the measurement cables and the current injection cables according to the test to be
performed (See
).
2�-
Connect the power supply cable. The device is designed to work at 230 V
~,
50/60 Hz.
Make sure the voltage is correct before plugging in the device. In the event of overvoltage,
the
GETEST
is protected by an F250 mA fuse.
Note:
Connect the device to a line or generator capable of supplying the required power:
Required power ≥ (600 V x Current to inject)
3�-
Activate the main switch of the device. The POWER LED will turn on.
4�-
Activate wireless connection between the smartphone and
GETEST,
via the smartphone settings.
The smartphone detects
GETEST
using the code that appears on the label located on the side of the
device.