Range:
-19999 M ... 99999 M.
Default value:
920.00
Note:
prL
>
prH
will cause the alarm to be disabled.
4�6�3�4� ALARM HIgH VALUe
This screen is used to configure the high value of the alarm,
prH
.
The screen flashes between the symbol and the configured value, (
).
figure 34:Alarm high value screens�
To edit the parameter, press the
button.
To modify the value of the selected digit, press the
button repeatedly.
To jump to the next digit, press the
button
Once at the desired value, validate by pressing the
button.
You can now select the position of the decimal point, which will be flashing.
To select the position of the decimal point, press the
button.
Validate by pressing the
button. The unit goes to unit configuration.
To select the unit, press the
button repeatedly.
The unit selected is displayed in red.
Once at the desired unit, validate by pressing the
button.
The unit goes back to the screen shown in
�
To move to the next parameter on the menu, press the
button.
Range
: -19999 M ... 99999 M.
Default value:
1150.0
Note:
prL
>
prH
will cause the alarm to be disabled.
4�6�3�5� ALARM Type
This screen is used to select the alarm functionality (see section
.
The screen flashes between the symbol and the configured value (
)
figure 35:Alarm types screens�
To edit the parameter, press the
button.
32
DHB-302 DHB-324
Instruction Manual
Содержание DHB-302
Страница 1: ...INSTRUCTION MANUAL M044B01 03 17A Single phase Vac analyzer DHB 302 DHB 324...
Страница 2: ...2 DHB 302 DHB 324 Instruction Manual...
Страница 64: ...Figure 60 Dimensions of the DHB 3xx 64 DHB 302 DHB 324 Instruction Manual...
Страница 66: ...8 CE CERTIFICATE 66 DHB 302 DHB 324 Instruction Manual...
Страница 69: ...69 Instruction Manual DHB 302 DHB 324...