Configuration values
Table 48:Configuration values: Latch�
Latch
Possible values
Yes
No
Note:
If the device is reset, the status of alarms is deleted and all alarms will return to the programmed
standby status, provided that the condition that triggered them has been resolved.
Press key
to access the next programming step.
6�25�6�- DISCONNECTION DELAY
The alarm disconnection delay is programmed on this screen in seconds.
Press key
for 3 seconds to edit the value. The
icon appears at the top of the screen.
To enter or modify the value, press the
key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to
modify the other values.
To validate the data, press
for 3 seconds and the
icon will disappear from the display.
Configuration values
Table 49:Configuration values: Disconnection delay�
Disconnection delay
Minimum value
0 seconds
Maximum value
9999 seconds
Press key
to access the next programming step.
61
Instruction Manual
CVM-C11