On the display screens the lower area disappears after 3 seconds without pressing any key.
It reappears by pressing the key
.
4�4�3�- CENTRAL AREA
The different display and setup menus for the device are accessed from the central area.
All instantaneous, incremental and demand parameters in various formats are also displayed:
Numeric representation of one, three and up to four parameters at the same time.
Analogue representation.
Graphical representation.
Representation on a bar chart.
A bar chart is displayed for instantaneous and demand parameters,
, which shows the
current instantaneous value, maximum and minimum values and pre-alarm and alarm zones
programmed.
Figure 34: Description of the bar chart�
If an alarm has not been programmed for the parameter, the pre-alarm and alarm zones shown
in the bar chart are calculated.
Figure 35: Calculation of the bar chart�
The calculation formulas are:
Neutral-phase voltage and neutral voltage
L
= Primary rated voltage* 0.9
H
=
Primary rated voltage * 1.1
Min
=
L
* 0.8
Max
=
H
* 1.2
P
L
=
L
+ ((
H
-
L
) * 0.1)
P
H
=
H
- ((
H
-
L
) * 0.1)
50
CVM-A1000 - CVM-A1500
Instruction Manual