-- Supply network analyzer CVM-144 (HAR) ----- User's manual --- Page No. 54
12.- APPENDIX A: Second SET-UP of the CVM-144
A second SET-UP menu is accessible in order to perform the configuration of
the CVM-144 with other features different from factory-supplied ones.
To access this menu proceed as follows:
-
Being the CVM-144 powered off, simultaneously press "
", "
max
" and
"
min
" keys.
-
Holding these keys pressed, powered the CVM-144 on.
When this option of the 2
nd
Setup menu is accessed, the following message
will be shown in screen during some seconds
Set
UP
Inic
12.1.- Communication setting
a.- Communication protocol: MODBUS
SET
PROT
Protocol:
BUS
(
MODBUS
(c)
(BUS) protocol
- "
" key: to validate the choice and pass to the next set-up screen: