Cipax CPX 23001 Скачать руководство пользователя страница 3

3/10 

 

Installation manual  

Closed Tank1350L/3000L/4000L/5000L/6000L 

Edition 2022-01-17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

General information 
The  CPX  Closed  Tank  is  rotation  moulded  in  impact  and  age 
resistant polyethylene plastic, intended for: 
- Wastewater, both grey water (bath, shower and laundry) and 
toilet/black water (economical flush version). 
- Rainwater collection. 
-  Storage  of  drinking  water.  FC-approved  product  (Food  Con-
tact).  
 

The tank is not intended to be used as a septic tank.  

  
The  tank  comes  with  a  standard  lockable  lid,  also  rotationally 
moulded in polyethylene plastic. The lid is tested and approved 
by  RISE  (SP)  according  to  the  Boverket  handbook  on  "Child-
proof wells" and SP method 0487 penetration test edition 3.  
 The tank can be installed both above and below ground.  
 
Dimensions 

 

Warning  

Never enter a sewage tank that has been brought into use. 

Gases can cause unconsciousness and immediate danger to life!  

Before installation 
A permit may be required for use as a sewage tank. Please con-
tact the Environmental & Health Protection Office (MHK) of the 
relevant  municipality  before  installation.  Maximum  allowed  dis-
tance and  suction  height to  sewerage emptying  vehicles should 
be investigated for the site before installation.  
 
Equipment 
The  tank  can  be  equipped  with  e.g.  level  alarm,  enhancement 
neck in different heights and rainwater kit for irrigation. 
See 

www.cipax.com

  for  more  information  on  equipment  and 

products.  

  

Handling 
The  tank,  equipment  and  accessories  should  be  handled  with 
care. Keep away from objects that could damage them. On re-
ceipt  and  before  installation,  inspect  the  products  carefully  for 
possible damage. The tank is delivered standing on an EU pallet.  
  
Lifting the tank 
The tank should be  lifted with soft  slings that can be  threaded 
through  the  moulded  lifting  loops.  Only  empty  tanks  may  be 
lifted and transported. 
  
Safety 
The lid is opened and closed with a tool, such as a 16 mm sock-
et wrench. The lid should always be in the locked position when 
installed on the tank. 

Pit

 

Choose  a  location  where  there  will  be  sufficient  slope  (~2%
>~2cm/m) for drainage pipes and where the soil is considered to 
be well drained and firm. Where there is a risk of groundwater 
ingress into the pit, it is advantageous to provide drainage out of 
the pit. The minimum size of the pit should be 500mm around 
the tank. Leave sufficient space for the installation of pipes and 
fittings.  
  
The tank should not be located where there is a risk of it being 
run  over  by,  e.g,  a  car  or  similar.  The  groundwater  level  must 
not rise to the inlet pipe. Avoid soil that is boggy or loose. Con-
sideration  should  also  be  given  to  the  frost  depth  at  the  site.  
Please document all or part of the installation with photographs 
and sketched drawings for future reference. 
 
Preparation of the pit 
The  tank  should  be  placed  on  a  well  levelled  and  well  drained 
gravel or sand bed at least 150 mm thick, without sharp stones 
or similar objects that could damage the tank. See table below 
for maximum installation depth. If possible, compress the gravel/
sand bed with a soil compactor. 
  

1350L 

CPX 23013 

3000L 

CPX 23020 

3000L 

CPX 23001 

4000L 

CPX 23031 

5000L 

CPX 23041 

6000L

 

CPX 23060 

 

Art.no  LxWxH (mm) 

Inlet height (mm) 

23013  1950x1200x1000  735 
23020  2350x1700x1350  1070 

23031  2600x2350x910  755 

Volume (L) 
1350 
3000 

4000 

3000 

23001  2350x2350x1000  770 

5000 

23041  2600x2350x1200  955 

6000 

23060  3400x2600x1175  1027 

Содержание CPX 23001

Страница 1: ...l avplanad och v l dr nerad grus eller sandb dd utan vassa stenar eller liknande som kan skada tanken Se tabell nedan f r maximalt nedgr v ningsdjup Komprimera g rna grus sandb dden med markvibra tor...

Страница 2: ...som har anslutningsplan p samma h jder Tankarna b r ha ett av st nd p minst 500 mm om tankarna r nedgr vda Ventilation Tanken med dess r rdragning m ste ha en bra ventilation f r att fungera tillfreds...

Страница 3: ...ully for possible damage The tank is delivered standing on an EU pallet Lifting the tank The tank should be lifted with soft slings that can be threaded through the moulded lifting loops Only empty ta...

Страница 4: ...tion surfaces at the same heights The tanks should be spaced at least 500 mm apart if they are buried Ventilation The tank and its pipework must have good ventilation to func tion properly Either via...

Страница 5: ...rlag av grus eller sand som er minst 150 mm tykt godt planert og veldrenert uten spisse steiner eller lignende som kan skade tanken Se tabellen nedenfor for maksi mal nedgravningsdybde Komprimer gjern...

Страница 6: ...er i samme h yder Tankene b r ha en avstand p minst 500 mm dersom de er gravd ned Ventilasjon Tanken og de tilh rende r rene m ha god ventilasjon for fungere tilfredsstillende Enten via avl pet med lu...

Страница 7: ...ei ole ter vi kivi tai vastaavia jotka voivat vahingoittaa s ili t Katso alla olevasta taulukosta suurin mahdollinen hautaussyvyys Tiivist sora hiekkapohja mielell n maantiivist j ll Ennen asennusta...

Страница 8: ...S ili iden et isyy den on oltava v hint n 500 mm jos s ili t on haudattu Ilmanvaihto S ili ss ja sen putkistossa on oltava hyv ilmanvaihto toimiak seen tyydytt v sti Joko viem rin kautta jossa on tuu...

Страница 9: ...i liivapadjal milles ei oleks teravaid kive ega muud mis v iks mahutit kahjustada Maksimaalse s gavuse kohta vt tabelit allpool Tihendage kruusa liivapatja vibroplaadiga Enne paigaldamist Kanalisatsio...

Страница 10: ...tel k lgedel mille henduskohad on samal k rgusel Ma hutite kaugus teineteisest maa sisse kaevatuna peab olema v he malt 500 mm Ventilatsioon Mahutil ja t mbetorudel peab olema hea ventilatsioon et k i...

Отзывы: