Total Solution for Industrial Automation
12
Hybrid Xpanel User’s Manual
3
Specification
3.1
General Specification
Items
Specification
Standards
Operating
Temperature
-10 ~ 55 ℃ (14 ~ 131℉)
Preserving
Temperature
-25 ~ 70 ℃ (-13 ~ 158℉)
Operating
Humidity
Relative Humidity 10 ~ 95%, No condensation
Preserving
Humidity
Relative Humidity 10 ~ 95%, No condensation
Vibration
Resistance
Frequency (pps)
Continuous Vibration
Intermittent Vibration
Count
IEC61131-2
Acceleration
(㎨)
Amplitude
(mm)
Acceleration
(㎨)
Amplitude
(mm)
5 ≤ f < 9
9 ≤ f ≤150pps
-
1.75
-
3.5
10 times for
each
direction X,
Y, Z
9 ≤ f ≤150pps
4.9 {0.5G}
-
9.8 {1G}
-
Shock
Endurance
Maximum shock acceleration: 147 ㎨ (15G)
Duration time: 11ms
Pulse wave : a sine half-wave pulse (3 times for each direction ±X, ±Y, ±Z,
total on 3 times)
IEC61131-2
Noise
Immunity
Square wave
impulse noise
±2kV, For 10 consecutive minutes
CIMON Internal
Test Standard
Electrostatic
Discharge
Immunity
Voltage: ±4kV(Discharge by contact), ±8kV(Air Discharge)
IEC61131-2
IEC61000-4-2
Radiated EMF
Noise
80~1000MHz, 10V/m
IEC61131-2
IEC61000-4-3
FAST transient
burst Noise
Power Supply
±2kV
IEC61131-2
IEC61000-4-4
Digital / Analog input output
(AC)
±2kV
Digital / Analog input output
(DC)
±1kV
Ambient
Conditions
Avoid corrosive gas and excessive dust
Operating
Altitude
≤ 2000m
IEC61131-2
Pollution Level
≤ 2
IEC61131-2
Cooling System
Air natural cooling