2-22
Installation
3916 Service Delivery Switch
Hardware Installation and Start-up Manual
009-3226-001 Standard Revision E
Copyright
©
2013-2015 Ciena
®
Corporation
July 2015
Procedure 2-7
Mounting the Chassis and Installing Supplemental
Ground in a Frame Installation
Note:
A supplemental ground connection is required for 3916 DC
Standard installations. The supplemental ground connection is optional for
3916 AC Standard and 3916 Dual AC Standard installations. A
supplemental ground connection is not required or available for mini
chassis systems. For systems that do not require a supplemental ground
connection see
“Mounting the Chassis (Supplemental Ground not
required) in a Frame Installation” on page 2-24
for a procedure.
If your installation site allows access to the left side of the chassis, you can
install the supplemental ground connection after the chassis is mounted.
However, if you will not be able to access the ground lug location after it is
mounted, you will need to install the supplemental ground connection before
mounting the chassis in the cabinet or frame. For more information see
“Grounding the Chassis” on page 2-6
The following procedure explains how to mount the chassis and connect the
3916 to supplemental ground when the 3916 is installed in a frame.
Step
Action
1
If this is a 3916 Standard system installation, determine if the installation site
will allow you to access the ground location on the left side of the chassis after
mounting. See
.
Do one of the following:
•
if the ground location will not be accessible — proceed to
•
if the ground location will be accessible — mount the chassis in the
desired installation location, using the installed brackets and customer
supplied mounting hardware. See
“Installing the Mounting Brackets for a
19-inch Frame Installation” on page 2-18
for detailed instructions.
Note:
The 3916 comes with the brackets required for mounting in a 19-inch
frame. A 23-inch frame mounting option is available but requires separately
orderable brackets. The mounting instructions for both bracket sizes are the
same.
2
Route the supplemental ground cable through the cabinet or installation site.
3
Insert the ground wire into the customer supplied ground lug. Using a ratchet
crimper, crimp the ground lug.
Note:
The ground lug should be a 2 hole lug @ 5//8 centers and with hole
size for #10 or 1/4” screw.