EN-7
Performance of chillers and free cooling modules
AQUACIAT
FREE COOLING
702V
800V
900V
1000V
1100V
1200V
1500V
1650V
1800V
High-per
for
mance (HP) version
Chiller's cooling capacity (1)
kW
185
206
246
265
286
327,0
373,0
429,0
483,0
Chiller's absorbed power
kW
60,3
69,7
81,5
89,6
100,2
110,7
127,6
145,6
163,2
Chiller's EER efficiency
3,08
2,95
3,02
2,96
2,85
2,96
2,92
2,95
2,96
Lw/Lp HP version (3)
dB(A)
90/58
93/61
95/63
96/64
98/66
Free cooling module
1 V - 2 R
2 V - 2 R
Cooling capacity (2)
kW
62,9
66,1
70,9
72,8
74,5
117,7
126,2
134,5
140,9
Absorbed power
kW
4,0
4,0
4,0
4,0
4,0
8,0
8,0
8,0
8,0
Free cooling EER efficiency
15,73
16,53
17,73
18,20
18,63
14,71
15,78
16,81
17,61
Lw/Lp HP version (3)
dB(A)
85 / 53
88 / 56
Free cooling module
1 V - 4 R
2 V - 4 R
Cooling capacity (2)
kW
91,7
95,2
100,5
102,4
104,1
173,7
183,7
193,1
200,0
Absorbed power
kW
4,0
4,0
4,0
4,0
4,0
8,0
8,0
8,0
8,0
Free cooling EER efficiency
22,93
23,80
25,13
25,60
26,03
21,71
22,96
24,14
25,00
Lw/Lp HP version (3)
dB(A)
86 / 54
89 / 57
Low Noise - LN and Xtra Low Noise - XLN versions
Chiller's cooling capacity (1)
kW
181,0
200,0
241,0
258,0
278,0
321,0
364,0
421,0
471,0
Chiller's absorbed power
kW
60,4
70,6
81,7
90,9
102,0
110,9
129,6
146,0
164,4
Chiller's EER efficiency
3,00
2,83
2,95
2,84
2,72
2,89
2,81
2,88
2,87
Lw/Lp LN version (3)
dB(A)
84/52
85/53
84/52
84/52
85/53
91/59
90/58
91/59
91/59
Lw/Lp XLN version (3)
dB(A)
81/49
82/50
81/49
81/49
83/51
87/55
87/55
87/55
88/56
Free cooling module
1 V - 2 R
2 V - 2 R
Cooling capacity (2)
kW
57,1
59,6
63,4
64,8
66,1
107,5
114,4
121,0
126,0
Absorbed power
kW
2,54
2,54
2,54
2,54
2,54
5,08
5,08
5,08
5,08
Free cooling EER efficiency
22,48
23,46
24,96
25,51
26,02
21,16
22,52
23,82
24,80
Lw/Lp LN version (3)
dB(A)
78 / 46
81 / 49
Lw/Lp XLN version (3)
dB(A)
76 / 44
79 / 47
Free cooling module
1 V - 4 R
2 V - 4 R
Cooling capacity (2)
kW
78,5
80,9
84,3
85,5
86,6
150,3
157,2
163,5
167,9
Absorbed power
kW
2,54
2,54
2,54
2,54
2,54
5,08
5,08
5,08
5,08
Free cooling EER efficiency
30,91
31,85
33,19
33,66
34,09
29,59
30,94
32,19
33,05
Lw/Lp LN version (3)
dB(A)
79 / 47
82 / 50
Lw/Lp XLN version (3)
dB(A)
77 / 45
80 / 48
(1) Cooling capacity based on: C12°C/+7°C, MEG 30% and condenser air inlet tempe35°C.
(2) Cooling capacity of free cooling module based on: Water inlet +12°C, MEG 30% and outdoor air tempe2°C.
(3) Overall sound power level (Lw) overall sound pressure level (Lp) measured at 10 metres in a free field, as per ISO 3744