Disappearance of the causes of the stoppage may pose the risk of danger during restarting.
■
Disconnect the electrical supply to the unit before carrying out any work.
■
Only personnel qualified to perform electrical work may carry out installation and maintenance
work.
Before connecting the unit to the network, ensure that the voltage matches that indicated on the data plate (230
V/1-ph/50-60 Hz).
COADIS LINE™
AC Asynchronous Motor ( 230V/50Hz)
HEE Brushless Motor ( 230V/50Hz)
612
622 - 624
632 - 634
612
622 - 624
632 - 634
Input power
W
A
W
A
W
A
W
A
W
A
W
A
Motor
code
V5
75
0,33
75
0,33
98
0,43
35
0,18
36
0,18
57
0,40
V4
45
0,20
45
0,20
73
0,32
15
0,09
14
0,09
32
0,28
V3
38
0,16
38
0,16
59
0,26
11
0,07
10
0,07
22
0,17
V2
28
0,12
28
0,12
48
0,21
7
0,04
7
0,04
15
0,13
V1
19
0,08
19
0,08
35
0,15
5
0,02
5
0,02
9
0,10
An earth connection is compulsory. CIAT shall not be liable for incidents resulting from faulty or non-
existent earthing. Always follow the circuit diagram delivered with unit.
Circuit diagrams for customer applications should be based on the diagrams supplied:
■ Unit wiring for 2-tube systems, without condensate pump (Fig. 10).
■ Unit wiring for 4-tube systems, without condensate pump (Fig. 11).
■ Unit wiring for 2-tube systems with an electric heater using 2 heating elements, without condensate pump (P=900
or 1200W max) (Fig. 12).
Note: if necessary, the output of the 300W electric heater can be reduced by removing the shunt positioned
between terminals 8 and 9.
CIAT
recommends using a system that controls the unit in relation to the temperature of the water (to actuate the
valve(s) and the use of an electric heater.
All electrical connections are fed into the electrics box marked with the symbol
.
The electrics box is equipped with a cable grommet to facilitate the routing of the cables to the terminal block.
To access the electrical terminal block:
Disconnect the device from the electrical power supply. Use a screwdriver to undo, but not remove, the lateral
retaining screw on the electrical box casing (Fig. 13 - a).
Modifying the motor speeds:
Always use a screwdriver when performing cabling operations.
COADIS LINE™
offers a choice between two types of motor technology:
Asynchronous and Brushless (low consumption).
■
The asynchronous motor:
To optimise the unit's performance and depending on the type of control used. The unit has five speeds numbered
V1 to V5 connected to the terminal block in the electrics box (V1= low speed and V5= high speed).
The customer must cable the speeds for the thermostat at the top of the terminal block between V1 and V5.
4 - INSTALLATION AND CONNECTIONS
EN-23
COADIS LINE
TM
600
Содержание COADIS LINE 600
Страница 1: ...COADIS LINE TM 600 05 2022 EN7521261 02 Instruction manual...
Страница 2: ...35kg 50 C 10 C COADIS LINETM 600 II...
Страница 3: ...Fig 1 g h k b j d j e c f a III COADIS LINETM 600...
Страница 5: ...Fig 4 Recommended Visual 360 Visual 180 Pr conis 600mm 300 mini a b V COADIS LINETM 600...
Страница 6: ...Fig 5 45 a c d b COADIS LINETM 600 VI...
Страница 7: ...Fig 6 Fig 7 Fig 8 a a b 131 5 202 67 5 157 40 S1 S E E1 60 18 5 VII COADIS LINETM 600...
Страница 10: ...Fig 13 Fig 14 a a b Fig 15 a Fig 16 a b Fig 17 COADIS LINETM 600 X...
Страница 11: ...Fig 18 a b c d e f g XI COADIS LINETM 600...
Страница 12: ...Fig 19 a b Fig 20 a b Fig 21 COADIS LINETM 600 XII...
Страница 31: ......