6 - ELECTRICAL CONNECTION
Table of minimum and maximum cable sections (per phase) for connection to the units
AQUACIAT
POWER
ILD ST / ILD HE
Max. connectable section
(1)
Calculation of favourable case:
Calculation of unfavourable case:
Standard
lug
Narrow
lug
Recommended
max width lug
Section
(2)
Max length for a
voltage drop < 5% Cable type
(3)
Section
(2)
Max length for a
voltage drop < 5% Cable type
(3)
mm²
(per
phase)
mm²
(per
phase)
mm
mm²
(per phase)
m
-
mm²
(per phase)
m
-
602
2x70
2x95
21
1 x 50
200
XLPE Copper
2 x 50
388
PVC Copper
650
2x70
2x95
21
1 x 50
180
XLPE Copper
2 x 50
358
PVC Copper
800
2x70
2x95
21
1 x 70
210
XLPE Copper
2 x 70
380
PVC Copper
900
2x70
2x95
21
1 x 70
190
XLPE Copper
2 x 70
350
PVC Copper
902
2x70
2x95
21
1 x 70
180
XLPE Copper
2 x 70
350
PVC Copper
1000
2x70
2x95
21
2 x 35
160
XLPE Copper
2 x 95
400
PVC Copper
1150
2x95
2x185
24,5
2 x 50
200
XLPE Copper
2 x 120
430
PVC Copper
1200
2x95
2x185
24,5
2 x 50
190
XLPE Copper
2 x 150
490
PVC Copper
1400
2x95
2x185
24,5
2 x 70
220
XLPE Copper
2 x 150
420
PVC Copper
1600
2x95
2x185
24,5
2 x 70
190
XLPE Copper
2 x 185
430
PVC Copper
1800
2x240
2x240
37
2 x 95
230
XLPE Copper
2 x 240
470
PVC Copper
2000
2x240
2x240
37
2 x 95
210
XLPE Copper
2 x 240
430
PVC Copper
(1) Connection capacities actually available for each machine. These are defined according to the connection terminal size, the electrical box access opening dimensions
and the available space inside the electrical box.
(2) Selection simulation result considering the hypotheses indicated.
(3) If the maximum calculated section is for an XLPE cable type, this means that a selection based on a PVC cable type can exceed the connection capacity actually
available. Special attention must be given to selection.
The protection against direct contact at the electrical connection point is compatible with the addition of terminals extension. The installer must determine whether
these are necessary based on the cable sizing calculation.
6.4 - Power cable access routing
The power cables for devices in the range are routed into the electrical box from underneath the unit.
A removable aluminium plate on the base of the electrical cabinet provides access for the power cables.
It is important to check that the power cable bend radius is compatible with the connection space available inside the electrical
cabinet.
Refer to the certified dimensional drawing for the unit.
Connection expansion box
This accessory is used to strip the power cable before it is routed inside the unit's electrical cabinet, and must be used when the
cable bend radius is not compatible with the space available inside the electrical cabinet. The "connection expansion box" accessory
provides mechanical protection for the stripped cable before it is routed inside the electrical cabinet.
It is recommended to use this accessory in the following cases:
Unit placed on the ground and the use of steel wired armoured (SWA) cables.
Unit placed on the ground and use of a rigid power cable with a section > 250 mm
2
.
EN-25
AQUACIAT
POWER
ILD