6 - CONNECT TOUCH CONTROL: DETAILED MENU STRUCTURE
6.3 Network parameters
Icon
Displayed text *
Description
Name
Modbus RTU Config.
Modbus RTU Configuration
MODBUSRS
Modbus TCP/IP Config.
Modbus TCP/IP Configuration
MODBUSIP
* Displayed in French by default.
Modbus RTU Config. Menu – MODBUSRS
No. Name
Status
Default Unit Displayed text *
Description
1
modrt_en
no / yes
no
-
RTU Server Enable
Enabling RTU Server: Modbus RS [modrt_en] and Modbus IP [modip_en] cannot be
enabled at the same time. If both are set to ‘yes’, Modbus IP will be automatically disabled.
2
ser_UID
1 to 247
1
-
Server UID
Server unique identifier
3
metric
no / yes
yes
-
Metric Unit
Metric unit
4
swap_b
0 to 1
0
-
Swap Bytes
Swap bytes
5
0 = Big Endian
0 = Big Endian
6
1 = Little Endian
1 = Little Endian
7
baudrate
9600 to 38400 9600
-
Baudrate
Baud rate
8
0 = 9600
0 = 9600
9
1 = 19200
1 = 19200
10
2 = 38400
2 = 38400
11
parity
0 to 4
0
-
Parity
Parity
12
0 = No Parity
0 = No Parity
13
1 = Odd Parity
1 = Odd Parity
14
2 = Even Parity
2 = Even Parity
15
3 = Force Parity Low
3 = Force Parity Low
16
4 = Force Parity High
4 = Force Parity High
17
stop_bit
0 to 1
0
-
Stop bit
Stop bit
18
0 = One Stop Bit
0 = One Stop Bit
19
1 = two Stop Bits
1 = Two Stop Bits
20
real_typ
0 to 1
1
-
Real type management
Real type management
21
0 = Float X10
0 = Float X10
22
1 = IEEE 754
1 = IEEE 754
*Displayed in French by default.
Modbus TCP/IP Config. Menu – MODBUSIP
No. Name
Status
Default Unit Displayed text *
Description
1
modip_en
no / yes
no
-
TCP/IP Server Enable
Enabling Modbus IP Server: Modbus IP [modip_en] and Modbus RS [modrt_en] cannot be
enabled at the same time. If both are set to ‘yes’, Modbus IP will be automatically disabled.
2
ser_UID
1 to 247
1
-
Server UID
Server unique identifier
3
port_nbr
0 to 65535
502
-
Port Number
Port number
4
metric
no / yes
yes
-
Metric Unit
Metric unit
5
swap_b
0 to 1
0
-
Swap Bytes
Swap bytes
6
0 = Big Endian
0 = Big Endian
7
1 = Little Endian
1 = Little Endian
8
real_typ
0 to 1
0
-
Real type management
Real type management (floating point)
9
0 = Float X10
0 = Float X10
10
1 = IEEE 754
1 = IEEE 754
*Displayed in French by default.
6.4 Alarms menu
Icon
Displayed text *
Description
Name
Reset Alarms
Reset Alarm(s)
ALARMRST
Current Alarms
Current Alarm(s)
CUR_ALRM
Alarm History
Alarm History
ALMHIST1
* Displayed in French by default.
EN - 19 AQUACIAT
CALEO