EN - 25
BMS communication protocol (continued)
Remote alarm
register
(read-only)
Remote
measurement
register
(read-only)
Register 10:
FAN FAULTS (1 = fault detected)
Bit
Bit
0
Fan fault, stage 1, line 1
8
Fan fault, stage 1, line 2
1
Fan fault, stage 2, line 1
9
Fan fault, stage 2, line 2
2
Fan fault, stage 3, line 1
10
Fan fault, stage 3, line 2
3
Fan fault, stage 4, line 1
11
Fan fault, stage 4, line 2
4
Fan fault, stage 5, line 1
12
Fan fault, stage 5, line 2
5
Fan fault, stage 6, line 1
13
Fan fault, stage 6, line 2
6 N.U..
14 N.U..
7 N.U.
15 N.U..
Register 11:
FAN FAULTS (1 = fault detected)
Bit
Bit
0
Sensor or pressure fault, coil 1,
circuit 1
8
Sensor or pressure fault,
coil 2, circuit 1
1
Sensor or pressure fault, coil 1,
circuit 2
9
Sensor or pressure fault,
coil 2, circuit 2
2 N.U.
10 N.U.
3 N.U.
11 N.U.
4 N.U.
12 N.U.
5 N.U.
13 N.U.
6 N.U.
14 N.U..
7 N.U.
15 N.U..
Registers
Registers
100 and
101
Control setpoint, coil 1,
circuit 1
108 and
109
Temperature or pressure,
coil 1, circuit 1
102 and
103
Control setpoint, coil 1,
circuit 2
110 and
111
Temperature or pressure,
coil 1, circuit 2
104 and
105
Control setpoint, coil 2,
circuit 1
112 and
113
Temperature or pressure,
coil 2, circuit 1
106 and
107
Control setpoint, coil 2,
circuit 2
114 and
115
Temperature or pressure,
coil 2, circuit 2
116 and
117
Outdoor temperature