Test UPS on battery back-up, switch off utility supply and observe ‘backup indicator’ 

lights. Also your PC should continue to function normally.

1. Self-testing while Turn ON

    Before turning on the UPS, the red/yellow/green led will be bright twice by turns.

    then the UPS will be ready for operation.

2. Silence Function

    In Battery Mode, shortly press the switch will enable or disable the buzzer.

    But when UPS is low battery or overload, the buzzer can not be silenced.

3. Overload Protection

    When UPS is overloaded while operating, which is not solved by the user in time,

    it will cut off the output automatically after short time.

4. Autorun DC Start & AC Start

    In DC mode, UPS discharges till battery run out and cut off, UPS autorun when

    AC recover.

5. Low Battery shutdown

    When the battery is about to be exhausted, UPS will shut down automatically to

    protect battery’s life.

6. Turn Off UPS

    1. AC Normal   UPS will cut off the output and goes to AC standby mode by

                             pressing the switch.

    2. Backup         Press the switch, the UPS will be turned off after a long beep.

7. Manual Self-testing

    User need to check the UPS ready for operation, Press the botton two time quickly

    then UPS self test, UPS transfer AC to Backup and Backup to AC.

The trouble shooting chart covers most of the difficulties that you may encounter

under normal working conditions. If the UPS fails to operate properly, please review

the following steps before calling the service center.

1. Is the UPS plugged into a correct working outlet?

2. Is the line voltage within the rating specified?

3. Is the Fuse or Breaker / Circuit Protector on back panal open?

4. UPS has used long time > 2 Year that is short backup time or fault.

Please submit the following information when you call for service.

1. Model No. & Serial No.

2. Date of problem.

3. Full desciption of problem UPS.

OPERATION AND TEST THE UPS

TROUBLE SHOOTING

TROUBLE SHOOTING CHART

Red LED continuous

bright with a beep every

8 seconds

UPS can not be turned

ON

UPS is not connecting

to AC and overloaded

Please connect to AC

and reduce the load

Please check the AC

Input Voltage
Please send to the 

agency to repair

Replace the Fuse or Reset

the breaker, remove some

load and check if the load

is short-circuit or faulty

The input Fuse is burn

or Breaker is off

UPS suddenly turns to

Battery mode in spite of

utility line present

Save the data promptly

and Shut down the 

operating system

Backup time less than

1 minute (low battery)

Close load and recharge

immediately

Battery problem

Replace the new battery
Recharge the battery for

atleast 12 hours and

retest the backup time

Use UPS > 2 year

Replace the new battery

Charging unit fault

Please send to the

agency to repair

Use more load over
Battery is not fully

charged

AC Input voltage is too

low

The UPS is failure

Red LED continuous

bright with a beep every

1 seconds

Back-up time less than

specified

PLUTO

Specification 

Model

                          

PT800    PT1000     PT1050     PT1200    PT1500

Power Rate (VA/W)

      

800/480   1000/600   1050/630     1200/720   1500/900

Input Voltage

 

         220 Vac -34%, +32% (145-290 Vac)

Output Voltage (AVR)

 

            220 Vac +10% (198-242 Vac)

Output Voltage (Backup)

 

           220 Vac +3% (213.4-226.6 Vac) 

Battery Capacity

          SLA 12V 9.4Ah x 1              SLA 12V 9.4Ah  x 2

Backup Time

 

                     15-40min (Depened on Load)

Charging Time

                           Batt. Cap.90% in 3-6 Hours

Protection System

           Over / Under Voltage, Over Load, Short Circuit Protection

                             Low Battery Shutdown Fault and Battery Replacement

Transfer Time

 

                  4-6 msec

LED Display

           Normal, Backup, Overload, Low Battery, Battery Replacement

Audible Alam

                    Backup mode, Low battery, Overload, Fault

Control Program

                USB port & Cable with PowerManager software

AC Line Surge Protector

           1,000,000W in 100

µ

s

 / 160 Joules in 2 ms

Tel / ADSL Surge TVSS

  

            Tel / Fax / ADSL / RJ11 / RJ45

Standard Certification

    ISO9001/14001, TIS.1291 1-2553, 2-2553, 3-2555, CE : IEC62040

Environment

 

        -45

°

C / RH 0-90% Non condensing

Dimensions (WxHxD) mm.

       100x145x305                   123x155x335

Weight kg.               

6.2         7.3          10          11          12

Front Panel

Rear Panel

PT1050 / PT1200 / PT1500

PT800 / PT1000

1. Power    2. Overload    3. Normal    4. Backup

1. AC Input              4. USB Port

2. Auto reset CB         5. Tel / Fax Surge

3. Outlets

1

2
3
4

5

OUTPUT UPS

5

4

3

1

2

10

Smart µP Line Interactive

      UPS with Stabilizer

Risk of electrical shock.

Do not remove cover. 

No user serviceable part Inside.

Refer servicing to qualified person

Refer manual for environmental.

!

CAUTION

1

2
3
4

PT1050 / PT1200 / PT1500

PT800 / PT1000

3

1

2

4

5