2-5 Hot Gas Foreign Bodies Check
Check Point
Procedure
1) Hot Gas V/V leaking caused by foreign particles.
-
Check temperature at the arrowed area while ice
making.
(Normally below 50
ºF
)
* When 2 or 3 ice cubes are not be made out of 12.
1) If the Hot Gas V/V Out
area is higher than 50
ºF
during ice making
, press
ON/OFF Ice dispensing
button about 20 times using the Test Board.
2) If you do not have the Test Board, tap the Sol V/V with
soft hammer.
Check under the
welded area