Oil Applications

Approx. Watts

Wiring

Watts-Volts                  Circuit-Phase (amps)

/Sq. In.

Diag. #

PCN 100140 (P/N 052-304749-005)

PCN 100298 (P/N 052-304749-305)

.5kW - 240V

1-3Ph (1.3 amps)

2

#6

.75kW - 120V

1-1Ph (7 amps)

5

#13*

.75kW - 208V

1-3Ph (2.1 amps)

5

#12*

1.5kW - 120V 

1-1Ph (13 amps)

5

#7

1.5kW - 120V

2-1Ph (2 x 7 amps)

5

#8

1.5kW - 208V

1-3Ph (4.2 amps)

5

#4

1.5kW - 240V

1-1Ph (7 amps)

5

#10

1.5kW - 240V

1-3Ph (3.7 amps)

5

#3

2.25kW - 208V

1-1Ph (11 amps)

15

#13*

2.25kW - 208V

1-3Ph (7 amps)

15

#11*

3.0kW - 240V

1-1Ph (13 amps)

20

#13*

3.0kW - 240V

1-3Ph (8 amps)

20

#11*

4.5kW - 208V

1-1Ph (22 amps)

15

#7

4.5kW - 208V

2-1Ph (2 x 11 amps)

15

#8

4.5kW - 208V

1-3Ph (13 amps)

15

#1

4.5kW - 208V

2-3Ph (2 x 7 amps)

15

#2

6.0kW - 240V

1-1Ph (25 amps)

20

#7

6.0kW - 240V

2-1Ph (2 x 13 amps)

20

#8

6.0kW - 240V

1-3Ph (15 amps)

20

#1

6.0kW - 240V

2-3Ph (2 x 8 amps)

20

#2

6.0kW - 480V

1-1Ph (13 amps)

20

#10

6.0kW - 480V

1-3Ph (8 amps)

20

#3

PCN 100159 (P/N 052-304749-006)

PCN 100300 (P/N 052-304749-306)

2.5kW - 120V

1-1Ph (21 amps)

15

#7

2.5kW - 120V

2-1Ph (2 x 11 amps)

15

#8

2.5kW - 208V

1-3Ph (7 amps)

15

#4

2.5kW - 240V

1-1Ph (11 amps)

15

#10

2.5kW - 240V

1-3Ph (7 amps)

15

#3

10kW - 240V

1-1Ph (42 amps)

21

#7

10kW - 240V

2-1Ph (2 x 21 amps)

21

#8

10kW - 240V

1-3Ph (25 amps)

21

#1

10kW - 240V

2-3Ph (2 x 13 amps)

21

#2

10kW - 480V

1-1Ph (21 amps)

21

#10

10kW - 480V

1-3Ph (13 amps)

21

#3

WIRING GUIDE – OIL (NWHOSR)

Directions:

Step 1: Select the PCN number below which matches the PCN number on your heater.
Step 2: Choose your kW, Volts, phase, and number of circuits under your PCN number 

(you must know the kW and watt density

(watts/sq. in.) needs for your application)

.

Step 3: Note the Wiring diagram # for your selection.
Step 4: Go to Wiring Diagram sheet. Peel off the diagram that matches the # in step 3. Stick this to the inside of your electrical enclosure.*
Step 5: Peel off corresponding Volts, circuit-phase, and kW info from the Wiring Diagram sheet and stick to the designated spot on the

nameplate. (These labels will cover the maximum rating stamped on the nameplate.)**

Step 6: Wire Heater according to the sticker on the inside of your electrical enclosure (from step 4).

Oil Applications

Approx. Watts

Wiring

Watts-Volts                   Circuit-Phase (amps)

/Sq. In.

Diag. #

PCN 100108 (P/N 052-304749-001)

PCN 100255 (P/N 052-304749-301)

4.5kW - 120V

1-1Ph (38 amps)

15

#7

PCN 100116 (P/N 052-304749-002)

PCN 100263 (P/N 052-304749-302)

1.5kW - 480V

1-3Ph (2 amps)

5

#6

2.5kW - 240V

1-1Ph (11 amps)

15

#13*

2.5kW - 240V 

1-3Ph (7 amps)

15

#11*

4.5kW - 240V

1-1Ph (19 amps)

15

#7

4.5kW - 240V

2-1Ph (2 x 10 amps)

15

#8

4.5kW - 240V

1-3Ph (11 amps)

15

#1

4.5kW - 240V

2-3Ph (2 x 6 amps)

15

#2

4.5kW - 480V

1-1Ph (10 amps)

15

#10

4.5kW - 480V

1-3Ph (6 amps)

15

#3

PCN 100124 (P/N 052-304749-003)

PCN 100271 (P/N 052-304749-303)

5.0kW - 120V

1-1Ph (42 amps)

11

#7

5.0kW - 208V

1-3Ph (14 amps)

11

#4

5.0kW - 240V

1-1Ph (21 amps)

11

#10

5.0kW - 240V

1-3Ph (13 amps)

11

#3

PCN 100132 (P/N 052-304749-004)

PCN 100280 (P/N 052-304749-304)

3.0kW - 120V

1-1Ph (25 amps)

20

#13*

3.0kW - 208V

1-3Ph (9 amps)

20

#12*

6.0kW - 120V

1-1Ph (50 amps)

20

#8

6.0kW - 208V

1-3Ph (17 amps)

20

#4

6.0kW - 208V

2-3Ph (2 x 9 amps)

20

#5

4

* Half of the heating elements are used

** For E2, affix to sheet metal on outside of enclosure

Содержание VERSATHERM PE414-3

Страница 1: ...ss ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heater Failure to do so could result in personal injury or property dam age Heater must be installed or serviced by a qualified person in accordance with the National Electrical Code NFPA 70 The system designer is responsible for the safety of this equipment and should install adequate back up controls and safety devices ...

Страница 2: ... not fail safe it should not be used for temperature limiting duty Wiring to this device is the responsibility of the user FIRE HAZARD Since heaters are capable of devel oping high temperatures extreme care should be taken to A Provide minimum of 6 spacing from chamber and related piping to nearest combustible mate rial B Do not operate near combustible fluids or in combustible vapor or gas laden ...

Страница 3: ...mine the appropriate wiring diagram for your heater instal lation Figure 1 may be referenced as a general diagram of how a contactor and temperature control are used in conjunction with the specific wiring diagrams 6 Use ground fault protection equipment where electrical insula tion failure can cause process problems 7 When element wattages are not equal heaters must not be con nected in series 8 ...

Страница 4: ...der your PCN number you must know the kW and watt density watts sq in needs for your application Step 3 Note the Wiring diagram for your selection Step 4 Go to Wiring Diagram sheet Peel off the diagram that matches the in step 3 Stick this to the inside of your electrical enclosure Step 5 Peel off corresponding Volts circuit phase and kW info from the Wiring Diagram sheet and stick to the designat...

Страница 5: ... 1 3Ph 13 amps 11 3 20kW 240V 2 1Ph 2 x 42 amps 80 8 20kW 240V 2 3Ph 2 x 25 amps 80 2 PCN 100044 054 304745 004 PCN 100360 054 304745 404 3 0kW 120V 1 1Ph 25 amps 20 13 3 0kW 208V 1 3Ph 9 amps 20 12 6 0kW 120V 1 1Ph 2 x 25 amps 20 8 6 0kW 208V 1 3Ph 17 amps 20 4 6 0kW 208V 2 3Ph 2 x 9 amps 20 5 12kW 240V 1 3Ph 29 amps 78 11 24kW 240V 3 1Ph 3 x 34 amps 78 9 24kW 240V 2 3Ph 2 x 29 amps 78 2 Half of ...

Страница 6: ...K 1L2 2L1 2L2 1L1 Y E L L O W B L U E R E D Y E L L O W B L U E R E D O R A N G E B R O W N B L A C K O R A N G E B R O W N B L A C K L1 L2 Y E L L O W B L U E R E D O R A N G E B R O W N B L A C K Y E L L O W B L U E R E D 3L1 B L A C K R E D 3L2 B L A C K R E D 1L1 B R O W N O R A N G E 1L2 B R O W N O R A N G E 2L1 Y E L L O W B L U E 2L2 Y E L L O W B L U E B L A C K R E D B R O W N O R A N G ...

Страница 7: ...tructions for operation of your application Ensure your procedure includes A Make sure all electrical and piping connections are tight B Remove all air from the heater and piping MAINTENANCE ELECTRIC SHOCK HAZARD Disconnect all power before servicing heater Failure to do so could result in personal injury or property damage Heater must be serviced by a qualified person in accordance with the Natio...

Страница 8: ...304748 005 NWHSRG 06 040P E1 100095 156 304748 006 NWHOSR 06 04P5 E2 100255 156 304748 301 NWHOSR 06 04P5 E2 100263 156 304748 302 NWHOSR 06 005P E2 100271 156 304748 303 NWHOSR 06 006P E2 100280 156 304748 304 NWHOSR 06 006P E2 100298 156 304748 305 NWHOSR 06 010P E2 100300 156 304748 306 NWHSRG 06 018P E2 100327 156 304748 301 NWHSRG 06 018P E2 100343 156 304748 302 NWHSRG 06 020P E2 100351 156 ...

Отзывы: